background image

2

 32801000801

Specifications  subject to change without notice.

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air−conditioning equipment can be
hazardous due to system pressures, electrical components, and
equipment location (roofs, elevated structures, etc.).

Only trained, qualified installers and service mechanics should install,
start−up, and service this equipment.

Untrained personnel can perform basic maintenance functions such as
cleaning coils. All other operations should be performed by trained
service personnel.

When working on the equipment, observe precautions in the literature
and on tags, stickers, and labels attached to the equipment.

Follow all safety codes. Wear safety glasses and work gloves. Keep
quenching cloth and fire extinguisher nearby when brazing. Use care in
handling, rigging, and setting bulky equipment.

Read these instructions thoroughly and follow all warnings or cautions
included in literature and  attached to the unit. Consult local building
codes and National Electrical Code (NEC) for special requirements.

Recognize safety information. This is the safety−alert symbol 

!

 !

. When

you see this symbol on the unit and in instructions or manuals, be alert
to the potential for personal injury. Understand these signal words:
DANGER, WARNING, and CAUTION. These words are used with the
safety−alert  symbol. DANGER identifies the most serious hazards
which  will  result in severe personal injury or death. WARNING
signifies hazards which could result in personal injury or death.
CAUTION is used to identify unsafe practices which may  result in
minor personal injury or product and property damage. NOTE is used
to highlight suggestions which will result in enhanced installation,
reliability, or operation.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal
injury or death.

Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF
position. There may be more than 1 disconnect switch.
Lock out and tag switch with a suitable warning label.

EXPLOSION HAZARD

Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.

Never use air or gases containing
oxygen for leak testing or operating
refrigerant compressors. Pressurized
mixtures of air or gases containing
oxygen can lead to an explosion.

!

WARNING

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment
damage or improper operation.

Do not bury more than 36 in. (914 mm) of refrigerant pipe
in the ground. If any section of pipe is buried, there must be
a 6 in. (152 mm) vertical rise to the valve connections on
the outdoor units. If more than the recommended length is
buried, refrigerant may migrate to the cooler buried section
during extended periods of system shutdown. This causes
refrigerant slugging and could possibly damage the
compressor at start−up.

Summary of Contents for DLCSRAH09AAJ

Page 1: ...tarting the installation Images are for illustration purposes only Actual models may differ slightly TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 WIRING 5 DIMENSIONS OUTDOOR 6 CLEARANCES OUTDOOR 7 INSTALLATION TIPS 8 OUTDOOR UNIT INSTALLATION 8 ELECTRICAL DATA 11 CONNECTION DIAGRAMS 11 SYSTEM VACUUM AND CHARGE 12 START UP 13 TROUBLESHOOTING 13 ...

Page 2: ...entifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation WARNING ELECTRIC...

Page 3: ...king a downward arc in the connection pipe before it enters the wall to the indoor unit This will ensure that rain will drip from the connection pipe before it enters the wall Piping and the interconnecting wiring are field supplied Figure 1 is only a sketch Different models may differ slightly Table 2 lists the units covered in this document Table 2 Unit Sizes SYSTEM TONS kBTUh VOLTAGE PHASE OUTD...

Page 4: ... indoor height difference IU higher than OU ft m 33 10 33 10 33 10 33 10 66 20 66 20 82 25 98 30 Max Piping Length with no additional refrigerant charge per System Standard Piping length ft m 24 6 7 5 24 6 7 5 24 6 7 5 24 6 7 5 24 6 7 5 24 6 7 5 24 6 7 5 24 6 7 5 Total Max Piping Length per system ft m 82 25 82 25 82 25 82 25 98 30 98 30 164 50 213 65 Additional refrigerant charge between Standard...

Page 5: ...talled in a high Electromagnetic field EMF area and communication issues exists a 14 2 stranded shielded wire can be used to replace L2 N and S between outdoor unit and indoor unit landing the shield onto ground in the outdoor unit only EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Wires should be sized based on NEC and local codes CAUT...

Page 6: ... 81 554 27 64 702 31 89 810 31 89 810 31 89 810 Width W in mm 30 31 770 31 5 800 31 5 800 31 5 800 33 27 845 37 24 946 37 24 946 37 24 946 Depth D in mm 11 81 300 13 11 333 13 11 333 13 11 333 14 29 363 16 54 420 16 54 420 16 54 420 L1 in mm 19 2 487 20 24 514 20 24 514 20 24 514 21 26 540 26 5 673 26 5 673 26 5 673 L2 in mm 11 73 298 13 39 340 13 39 340 13 39 340 13 8 350 15 87 403 15 87 403 15 8...

Page 7: ...ounted at least 2in 50mm above the maximum anticipated snow depth 118in 300cm ormore 19in 48cm ormore onamultipleparallel unitarrangement 4in 10cm ormoreon asingleparallelunit arrangement 24in 60cm ormore 59in 150cm ormoreona multipleparallel unitarrangement 24in 61cm ormore onasingleparallel unitarrangement 9 8in 25cm ormorefor properairflow 24in 61cm or moreis recommended forservice 9 8in 25cm o...

Page 8: ...ld be firm stable and reliable Ensure there is no obstacle which may block the radiating air Strong wind A07350 Fig 5 High Wind Installation MAKE REFRIGERANT PIPING CONNECTIONS OUTDOOR UNIT IMPORTANT Use refrigeration grade tubing ONLY No other type of tubing may be used Use of other types of tubing will void manufacturer s warranty Do not open service valves or remove protective caps from tubing ...

Page 9: ...nit capacity and voltage 7 Ground unit in accordance with NEC and local electrical codes 8 Use lock nuts to secure conduit 9 Reinstall field wiring cover CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation S Be sure to comply with local codes while running wire from indoor unit to outdoor unit S Every wire must be connected firmly Loo...

Page 10: ...int Images are for illustration purposes only CAUTION In cold climates ensure the drain hose is as vertical as possible to ensure swift water drainage If water drains too slowly it can freeze in the hose and flood the unit NOTE Basepan built in with multiple holes for proper draining during defrost For applications where it is required to seal these holes and re direct the condensate drain rubber ...

Page 11: ...ble limits of the voltage range at which the unit will operate satisfactorily LEGEND FLA Full Load Amps MCA Minimum Circuit Amps RLA Rated Load Amps CONNECTION DIAGRAMS S L N 115 1 60 Main Power Supply 115 1 60 L N S L N Power to Indoor Unit CONNECTING CABLE OUTDOOR TO INDOOR GND Ground Indoor Signal High Voltage 115 1 60 115 1 60 FIELD POWER SUPPLY GND Indoor Signal High Voltage Indoor Unit Power...

Page 12: ...ow side valve A07361 Fig 14 Manifold Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum method is the best way to assure a system is free of air and liquid water see Fig 15 500 MINUTES 0 1 2 3 4 5 6 7 1000 1500 LEAK IN SYSTEM VACUUM TIGHT TOO WET TIGHT DRY SY...

Page 13: ...the systems are equipped with diagnostic code display LEDs on both the indoor and outdoor units The outdoor diagnostic display is two LEDs Red and Green on the outdoor unit board and is limited to very few errors The indoor diagnostic display is a combination of flashing LEDs on the display panel or the front of the unit There may be a few error codes displayed in the indoor unit that might relate...

Page 14: ...14 32801000801 Specifications subject to change without notice Copyright 2018 International Comfort Products CMNA 1025 Cobb Place Blvd NW Kennesaw GA 30152 ...

Reviews: