26
8.10 Automatic operation mode
When running in automatic mode, the air conditioner automatically selects one of the
following operation modes: cooling, heating or fan only according to the temp. difference
between room temp. (TA) and set temp. (TS).
TA
—
TS
Operation mode
TA
—
TS>2
℃
Cooling
-1
℃≤
TA
—
TS
≤
+2
℃
Fan-only
TA
—
TS<-1
℃
Heating (air-only for cooling only type)
at auto mode, the indoor fan blows automatically in selected mode.
8.11 Forced cooling function
A: Select forced cooling function with the forced cooling button or the switch.
B: The compressor is unconditionally turned on, after 30 minutes cooling operation whose fan
mode is set as low, the A/C operates at DRY mode with a set temp. of 24
℃
.
C: All protections of remote control cooling are available at forced cooling operation.
8.12 Forced Auto function
A: Select forced auto function with the forced auto button or the switch.
B: In forced auto status the A/C operates at remote control mode with a set temp. of 24
℃
.
8.13 Timer Function
8.14 Economic Running
Cooling: The set temperature rise 1
℃
per hour. Two hours later, the set temperature will
maintain as a constant and the air circulation is kept at low speed.
Heating: The set temperature decrease 1
℃
per hour. Two hours later, the set
temperature will maintain as a constant and the air circulation is kept at low speed (Cold air
proof function takes priority over all).
Auto: The economic running function operates in accordance with the selected running
mode by the auto mode.
Summary of Contents for CE-KF20GW/N1Y-H
Page 6: ...3 4 Outdoor unit MSH 07CRN1 MSH 07HRN1 3 5 Outdoor unit MSH 09CRN1 MSH 09HRN1 248...
Page 7: ...3 6 Outdoor unit MSH 12CRN1 MSH 12HRN1 530 315 290 750 110 62 590 285 249...
Page 8: ...4 Refrigeration cycle diagram 250...
Page 35: ...229 1 Features 1 1Compact design 1 2High efficiency and quiet operation...
Page 37: ...231 3 Dimensions 3 1 Indoor unit 3 2 Outdoor unit...
Page 40: ...234 6 Wiring diagram Indoor unit Outdoor unit...
Page 51: ...1 Features 1 1Compact design 1 2High efficiency and quiet operation 215...
Page 53: ...3 Dimensions 3 1 Indoor unit 3 2 Outdoor unit 217...
Page 54: ...4 Refrigeration cycle diagram 218...
Page 70: ...203 3 Dimensions 1 Indoor unit 7 9K 2 Indoor Unit 12K 3 Outdoor unit...
Page 75: ...208 7 Wiring Diagram 7 1 Indoor unit 7 9K 7 2 Indoor unit 12K...
Page 76: ...209 7 3 Outdoor unit M2OA 18HRIN2 Outdoor unit M3OA 27HRIN2...
Page 85: ...182 3 Dimensions 3 1 Indoor Unit MSG 09HRI MSG 07 09HRIN2 3 2 Indoor Unit MSG 12HR1...
Page 86: ...183 3 3 Indoor Unit MSG 12HRIN2 3 4 Outdoor Unit...
Page 90: ...187 Outdoor unit MSG 09HRI MSG 12HRI S N L...
Page 91: ...188 Indoor unit MSG 12HRIN2 Outdoor unit MSG 07HRIN2 MSG 09HRIN2 MSG 12HRIN2 N L S...
Page 101: ...1 Features 1 1Compact design 1 2High efficiency and quiet operation 158...
Page 103: ...3 Dimensions 3 1 Indoor unit MSG1 07 09C H RN2 3 2 Indoor unit MSG1 12C H RN2 280 160...
Page 104: ...3 3 Outdoor unit MSG1 07C H RN2 3 4 Outdoor unit MSG1 09C H RN2 161...
Page 105: ...3 5 Outdoor unit MSG1 12C H RN2 530 315 290 750 110 62 590 285 162...
Page 110: ...6 2 Heating cooling 6 2 1 MSG1 07HRN2 MSG1 09HRN2 167...
Page 111: ...6 2 2 MSG 12HRN2 168...
Page 122: ...1 Features 1 1Compact design 1 2High efficiency and quiet operation 140...
Page 126: ...3 Dimensions 3 1 Indoor unit 3 2 Outdoor unit 144...
Page 130: ...6 2 Heating cooling 148...
Page 144: ...3 Dimensions 3 1 Indoor unit 7000Btu h 9000Btu h 12000Btu h 132...
Page 145: ...3 2 Outdoor unit 133...
Page 153: ...117 3 Dimensions 3 1 Indoor unit 3 2 Outdoor unit 62 77 860 895 589 6 142 9 302 328 350...
Page 168: ...3 Dimensions 3 1 Indoor unit 3 2 Outdoor unit 12 5 102...
Page 171: ...6 Wiring diagram 6 1 MSG 24CR MSG 30CR MSG 24CRN2 MSG 30CRN2 220V 1Ph A2 A1 105...
Page 172: ...6 2 MSG 24HR MSG 30HR MSG 24HRN2 MSG 30HRN2 220V 1Ph A1 A2 106...
Page 173: ...6 2 MSG 30CR MSG 30CRN2 380V 3Ph 107...
Page 174: ...6 2 MSG 30HR MSG 30HRN2 380V 3Ph 108...
Page 182: ...1 Features 1 1Compact design 1 2High efficiency and quiet operation 66...
Page 190: ...3 3 Indoor unit MSG 18 21C H R N2 3 4 Outdoor unit MSG 05 07 09C H R N2 74...
Page 192: ...3 7 Outdoor unit MSG 21C H R N2 12 5 76...
Page 201: ...6 2 2 MSG 12HR B TYPE MSG 12HRN2 85...
Page 226: ...6 1 5 MSG 30CRN2 380V 50Hz A N 1 2 3 4 58...
Page 227: ...6 2 1 MSB 07HRN2 MSB 09HRN2 6 2 2 MSB 12HRN2 59...
Page 229: ...6 2 4 MSB 21HRN2 61...
Page 230: ...6 2 5 MSB 24HRN2 MSB 30HRN2 A1 A2 62...
Page 231: ...6 2 6 MSB 30HRN2 380V 50Hz 63...
Page 236: ...3 Dimensions 3 1 Indoor unit 18000 21000Btu h 3 2 Indoor unit 24000 30000Btu h 31...
Page 237: ...3 3 Outdoor unit 18000 3 4 Indoor unit 21000 30000Btu h 12 5 32...
Page 240: ...6 Wiring diagram 6 1 MSB 18CR MSB 21CR 35...
Page 241: ...6 2 MSB 24CR MSB 30CR 36...
Page 243: ...6 4 MSB 21HR 38...
Page 244: ...6 5 MSB 24HR MSB 30HR A1 A2 39...
Page 254: ...12 3 Dimensions 3 1 Indoor unit 5000 9000Btu h 12000Btu h...
Page 255: ...13 3 2 Outdoor unit 5000 9000Btu h 3 3 Outdoor unit 12000Btu h...
Page 258: ...16 6 Wiring diagram 6 1 Cooling only 5000 9000Btu h 12000Btu h...
Page 260: ...18 6 2 Heating cooling 5000 9000Btu h 12000Btu h...
Page 261: ...19 Outdoor unit...
Page 280: ...3 Dimensions 3 1 Indoor unit MSH 09HRDN1 3 2 Indoor unit MSH 12HRDN1 279...
Page 281: ...3 4 Outdoor unit MSH 09HRDN1 MSH 12HRDN1 530 315 290 750 110 62 590 285 280...
Page 282: ...4 Refrigeration cycle diagram 281...
Page 308: ...1 Features 1 3Compact design 1 4 ation High efficiency and quiet oper...
Page 312: ......
Page 313: ...4 Refrigeration cycle diagram...
Page 316: ......
Page 318: ......
Page 332: ...2 1 Features 1 1Compact design 1 2High efficiency and quiet operation...
Page 336: ...3 4 Outdoor unit MSH 07CR MSH 07HR MSH 09CR MSH 09HR 3 5 Outdoor unit MSH 12CR MSH 12HR 6...
Page 337: ...4 Refrigeration cycle diagram 7...
Page 345: ...7 2 1 2 MSH 12CR 15...
Page 346: ...7 2 2 Heating cooling 7 2 2 1 MSH 07HR MSH 09HR 16...
Page 347: ...7 2 2 2 MSH 12HR 17...