POWER (GREEN): This indicates that the unit is receiving power.

FAN (YELLOW): When rack temperature reaches 81

O

F (27

O

C), this LED will begin to flash indicating

that the fans have turned on. It will continue flashing proportional to the fan speed, as long as the fans
are on.

ALARM (RED): At the factory preset overtemp of 100

O

F (37

O

C), this LED will light indicating an over

temperature condition within the rack. See Alarm Set Point Button instructions below to change the 
overtemp alarm setting.

DISPLAY: The display will indicate the rack temperature and  provide a read-out of the following fault
codes during one of these conditions:

 

OVERTEMP: The temperature of the enclosure has risen above the alarm set point. Inspect 

 

airflow intake and output for obstructions. Additional cooling capacity may be required.

 

FAN FAULT: One or more of the fans has stopped. Check all fans for obstruction. 

 

If problem persists, call Technical Support at (800) 266-7225.

Models UQFP-2D & UQFP-4D/IUQFP-2D & IUQFP-4D

(UQFP-4D Model Shown)

POWER (GREEN)

DISPLAY

FAN (YELLOW)

ALARM (RED)

FRONT VIEW

Summary of Contents for UQFP Series

Page 1: ...asing the UQFP Series Ultra Quiet Fan Panel Please read these instructions thoroughly before installing this product PRODUCT FEATURES Reliable cooling with minimal noise Local and remote status notifi...

Page 2: ...Speed 310 mA 5V DC UQFP 2D IUQFP 2D RPM 1900 Full Speed Noise 24 dB Full Speed UQFP 4 UQFP 4D IUQFP 4 IUQFP 4D Current Draw 510 mA 5V DC UQFP 4 IUQFP 4 Airflow 100 CFM Full Speed 560 mA 5V DC UQFP 4D...

Page 3: ...ack temperature reaches 100O F 37O C this LED will light indicating an over temperature condition within the rack OVERTEMP ALARM OUTPUT This normally open dry contact closure will provide an alarm to...

Page 4: ...t Button instructions below to change the overtemp alarm setting DISPLAY The display will indicate the rack temperature and provide a read out of the following fault codes during one of these conditio...

Page 5: ...the Alarm Set Point Button until desired temperature is displayed Factory preset overtemp alarm set point is 100O F 37O C Adjustment range is from 95O to 115O F 35O to 46O C FAN FAULT OVERTEMP ALARM...

Page 6: ...o toggle between Fahrenheit and Celsius press and hold for 3 seconds OVER TEMP ALARM N O 5VDC 2A FAN FAULT ALARM N O PUSH CONTROL SETTINGS Press once to view the current overtemp alarm setting Each ad...

Page 7: ...vent at the top of side panels Do not place vent panels within six rackspaces below fan panel Cover any of these spaces If heat producing equipment is in the middle of the rack use a 3 space vent pane...

Page 8: ...ANY KIND EITHER EXPRESSED OR IMPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO THE MAXIMUM EXTENT PERMITTED BY APPLICABLE LAW IN NO EV...

Reviews: