1) Wire all rear terminal blocks in parallel, for multiple sequence operation.
2) Front system power up/down switch is wired in parallel with rear remote terminal block. When wired together
as shown, pressing front System Power UP/DOWN switch on ANY sequencer will initiate system sequencing.
3) If remote power UP/DOWN is required, wire dry contacts in parallel. (single pole, double throw, center off,
momentary switch)
4) Initiating system sequencing remotely: Sequencing can be initiated by either momentary dry contact or
maintained dry contact. Use of a maintained dry contact for system power up will reinitiate sequence after
power is restored from a power outage. When using maintained (not momentary) dry contact for remotely
controlling system sequencing, the front System Power UP/DOWN switches will be over-ridden.
NOTE:
A flashing power (green) LED indicates that the system sequencing has begun.
DELAY BETWEEN SEQUENCES
.75 second interval between
each outlet power up/down
1.5 second interval between
each outlet power up/down
2.25 second interval between
each outlet power up/down
7 second interval between
each outlet power up/down
SEQUENCE UP/DOWN START DELAY
If 2 or 3 sequencers are to be used ("chained") together:
sequencer
#1
sequencer
#2
sequencer
#3
sequencer #1
sequencer #2
sequencer #3
1 2 3 4
1 2 3 4
1 2 3 4
first on
last off
second on
second off
last on
first off
up
com
down
up
com
down
up
com
down
DIP SWITCH SETTINGS:
optional
Installer provided
remote Switch
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
Page 4
POWER
PDS-2x315R
- 115 Volt AC
- Two 12 Amp circuits (24 Amps total)
- Two 9' Power cords (14/3)
- Standard NEMA 5-15 plugs
PROGRAMMING
- Sequence delay start and interval between
outlets timing functions controlled via front
mounted dip switch
DIMENSIONS
- 19" Wide
- 1.75" High (1 space)
- 8.75" Deep
CONSTRUCTION
- 18 Gauge steel
- Black powder coat finish
OUTPUT
- 7 Rear outputs (1 uncontrolled)
- 24 Amps total load (max)
- 12 Amps per circuit (max)
- 115 Volt AC
INTERCONNECTION
- Rear remote control terminal block provides
remote system power up/down. Multiple units
maybe chained together via simple parallel
wiring
- Rear status terminal block, indicates
sequence complete (Relay contact closure)
PROTECTION
- Two 12 Amp circuit breakers located on front
panel