background image

8.

To  make  a  preliminary setting of the burner input,
determine  the manifold gas pressure required from
Table 2 and adjust the Combination Valve Main Gas
Pressure Regulator accordingly. See Section XI.

9.

To   determine  the  firing  rate  for  NATURAL  gas,
accurately  time  test dial for the number of seconds
for one revolution and use the following formula.  All
other gas utilization equipment must be off.

3600 x test dial size x BTU value

No. of seconds for one rev. test dial

Then divide by 1,000 for MBH value.

Example:   3600 x 1 x 1000

20

For PROPANE gas, consult your supplier for method of
determining firing rate.

10. Adjust combustion air shutter to provide a quiet, soft

blue flame with well defined orange and yellow tips 
for  NATURAL  gas  or  with  well defined yellow tips
for PROPANE gas.

11. The  combustion  air  adjustment  which  affects the

flame  length  has  been  set wide open for average
conditions. Decrease the combustion air if a longer,
softer flame is desired.

12. Check the operation of the burner; start  and stop  it

several   times   with   the   thermostat  or  operating
control.

13. With  the  burner  running, check the operation of all

limit and associated controls.

14. PERFORM THE FOLLOWING FINAL  ADJUSTMENTS

for  combustion  and  flue gas temperature. Take the
flue   gas   samples  and  temperature  immediately
ahead of the draft control.
A. The   flue   gas  temperature  should  be  above

325°F  but not exceeding 550°F. Excessive flue
gas  temperatures  will result in low efficiencies.
Low flue gas temperature may cause excessive
condensation.  Reset  gas  input if necessary to
adjust stack temperature.

B. Make  the  final  setting  of  the  combustion  air

shutter   by  checking  the  flue  gases  with  an
ORSAT

or     similar     combustion    testing

instrument.    The   carbon   monoxide   content
should   conform   to   local  codes,  or  in  their
absence,  to  the  level  specified  in  the United
States or Canadian Standard referenced on the
front   cover   of  this  manual;  and  the  carbon
dioxide  content  should be approximately 9.5%
for  NATURAL  and  12.1%  for  PROPANE,  or
within the limits prescribed by local codes.

15. Check  the  draft  control  to  make  sure there is no

spillage of flue products into the room.

16. FILL   OUT  THE  INSTALLATION  ADJUSTMENT

DATA TAG  and affix to the burner or gas utilization
equipment.

NOTE:  For subsequent normal starting and shut off
procedure, refer to CONSUMER INSTRUCTIONS  or to
the instruction plate mounted on the burner.

PART 2 

SERVICE

CONSUMER CAUTION: Do not tamper with the

unit or controls. If trouble occurs, contact a qualified
Service Technician.

= BTU/Hr.

=180,000 BTU/Hr. =180

DANGER: Be sure that  the Main and Pilot Manual

Shut-Off Valves, Combination Valve and Burner
Power Switch are turned OFF before removing any
parts for service.

WARNING: All cover plates, enclosed and guards

must be in place at all times except during
maintenance and servicing.

IX PILOT

The pilot is of the premix, blast type. The full force of
blower air is brought into the mixing tube where the
proper amount of gas is added through the pilot orifice.
This mixture is discharged through the pilot which
contains a perforated flame retention plate. The outer
holes diverge to spray the mixture against the side wall
of the pilot tip to provide flame retention. The mixture
through the center port provides the flame that contacts
the flame detection rod and also ignites the  main gas.

Surrounding the base of the pilot flame is a conical

shroud which protects the flame against extraneous air
currents and inhibits "blow-off" from an overly rich flame. 

The pilot gas orifice is the same size both for

NATURAL and PROPANE gas, consequently the gas
pressure required for PROPANE is lower than that
required for NATURAL gas.

CAUTION: Do not indiscriminately increase pilot

orifice size. Pilot troubles are rarely cured in this
manner and new troubles may be created.

Under normal conditions, with a slight negative

pressure in the combustion chamber, pilot operating
pressures are 3.5" W.C. NATURAL gas and 2.25" W.C.
PROPANE.

Some conditions which may require a change from the

normal setting include: extremely long tubing
connections between the regulator and pilot solenoid,
high negative or positive combustion chamber pressure,
actual air shutter setting and altitude extremes.

Do not subject the Pilot Solenoid or Pilot Regulator to

an inlet pressure over 14.0" W.C. See section VI PIPING
for high pressure gas. Note that the standard pilot
pressure regulator is not a tight shut-off and, during
standby, the outlet pressure will build up to the full inlet
pressure. 

The spark rod is located on the center line of the pilot

and is positioned so the high tension voltage will arc to
the inside of the center port of the retention plate (see
Figure 7).

The flame rod must be positioned as shown in Figure

7 so that the electronic control will detect a proper flame.
Note that it is slightly above the centerline of the pilot.

Both the spark and flame rods are current carrying

conductors and, along with their connecting wires, must
be kept free of contact with conductive metal parts of the
burner. Rod insulators and wire insulators should be
clean, dry and free of cracks.

Rods are made from heat resistant alloys and can be

expected to have a long service life. They should be
routinely inspected, however, for corrosion or loss of
metal.

The pilot air tube must be kept free of kinks or inside

obstructions and its inlet end must be positioned per
Figure 7, otherwise air flow could be reduced sufficiently
and adversely affect the pilot flame.

-6-

Summary of Contents for ECONOMITE F400B-33

Page 1: ...s or in the absence of local codes with Installation of Domestic Gas Conversion Burners ANSI Z21 8b 1993 and National Fuel Gas Code ANSI Z223 1 1992 or latest edition s available from American Nationa...

Page 2: ...is of one square inch free area per 1 000 BTU of the total input rating of all gas utilization equipment in the combined space One grille should be located within 12 inches of the ceiling the other wi...

Page 3: ...at transfer to the primary surfaces of the heat exchanger In most cases the existing combustion chamber liner formerly used for oil burner can be used if in good condition In the case of wet base boil...

Page 4: ...ing close to burner as shown in Figure 5 Use pipe joint compound approved for use with Liquid Petroleum Gases Piping must comply with local codes To obtain the maximum firing rate of 700 MBH the NATUR...

Page 5: ...bination Valve to OFF close Pilot Manual Shut Off Valve turn burner power on and set operating control to ON or thermostat to call for heat Let the blower run long enough to accomplish four air change...

Page 6: ...r Switch are turned OFF before removing any parts for service WARNING All cover plates enclosed and guards must be in place at all times except during maintenance and servicing IX PILOT The pilot is o...

Page 7: ...e switch plunger to push it past its operating point When running the actuator pulls the disk clear of the plunger To make a specific test of the interlock circuit 1 Turn burner power OFF 2 Turn Manua...

Page 8: ...justable for outlet pressure range of 2 0 W C to 5 0 W C Outlet pressure settings must be checked while the gas is flowing To adjust outlet pressure remove the seal cap for access to the adjusting scr...

Page 9: ...D AND THE BURNER IS LOCATED IN A BASEMENT CRAWL SPACE OR CONFINING SPACE CONTACT YOUR GAS SUPPLIER ABOUT INSTALLING A GAS LEAK WARNING DEVICE PROPANE GAS IS HEAVIER THAN AIR AND CAN SETTLE IN LOW AREA...

Reviews: