miface PB
Universal Interface Profibus DP / Serial Interface RS232/485/422
Page
3
microSYST Systemelectronic GmbH, Albert-Einstein-Straße 7, 92637 Weiden
Tel. +49 961 39166-0, Fax +49 961 39166-10, www.microsyst.de, [email protected]
1 General
Using the universal interface, Profibus DP output data are transmitted via
the serial RS interface, and frames received by the serial RS interface are
copied to the Profibus DP input data.
The mechanical design is laid out for top-hat rail mounting.
Settings for bus termination, address and options can be made simply by
using DIP switches.
2 Technical Data
Specifications
Interface 1:
Profibus DP
Baud rate:
9,6 kBaud…12 MBaud
Addresses:
0…126
Interface 2:
RS232 / 485 / 422
Baud rate:
1200 to 115200 baud
Data formats:
7 / 8 Bit
Parity:
7 Bit: none (2 stop bits),
8 Bit: even, odd, none (1 stop bit)
Operating voltage:
+12…+30 VDC
Power consumption:
approx. 200 mA at 12 VDC
approx. 100 mA at 24 VDC
Housing:
aluminium profile
Housing size:
26 x 105 x 70 mm (W x H x D)
Mounting:
to 35 mm DIN top hat rail
Protection:
Front panel: IP 00
Operating temperature:
0…+50 °C
Storage temperature:
-25…+60 °C