4
18
PE
Power grounding wire
19
220V
220V AC power supply access
20
220V
21
EX1
Exciting current
22
EX2
3.2
Separated wiring
Figure 2 Separated wiring diagram
When connecting the power cable, pay attention to select the appropriate voltage level wiring. For
different voltage levels, select 220V AC or 24V DC wiring to avoid power wiring faults.
When wiring, select the corresponding power terminal to connect to the power line according to the
product specifications, and then connect to the signal line according to the required output form. See
Table 3 for the specific meaning of the integrated electromagnetic flowmeter wiring terminals.
Table 3 Terminal definition of separated type
Terminal Symbol
Function
1
T
+
/A
RS485/RS232 communication output
RS232 grounding wire
RS485/RS232 communication input
2
RS232 GND
3
T
-
/B
4
I mA
4mA~20mA DC output;
Active output If passive
output Then pull out the
shorting piece
5
ICOM
Current output grounding wire
6
P
+
2-way flow pulse output/frequency output
7
PCOM
Pulse output grounding wire
8
TRH1
Inlet thermal resistance
9
TRH2
10
TRH3
11
TRL1
Outlet thermal resistance
12
TRL2
13
TRL3
14
EX1
Exciting current
15
EX2
Shielding network
DS1
16
SIG1
Electrode wire