2
IP protection
IP65, IP68: submersible, long-term working in water, suitable for instrument installation in
instrument well.
Environmental temp.
Working temp.: -20
℃
~60
℃
Storage temp.
-40
℃
~60
℃
Relative humidity
5%~90%
3 Electrical Connection
The Insert electromagnetic flowmeter converter can be divided into integrated converter and separated
converter, and the wiring diagram is shown in Figure 1 and Figure 2.
When wiring, please note:
a) RS485 communication cable needs to use two-core twisted pair shielded wire;
b) The same cable shall not be used for the power line and 4mA~20mA DC signal line. Two cables
shall be connected separately.
3.1
Integrated wiring
1
2
3
4
5
6
7
8
9
10
11
12
13
14
115
T-/B
RS232
T+/A
IOUT
POUT
COM
AH
AL
+3.3V
S1
S0
1S2
GND
COM
+24V
+IN
0V
1
2
Current
Passive
Active
Pulse
Passive
Active
RS232
1
3
RS485
RS485
RS232
1
2
4-20mA
Pulse
modbus
22
21
20
19
18
220V
220V
PE
-24V
+24V
E
X
2
E
X
1
16
17
Figure 1 Integrated wiring diagram
When wiring, select the corresponding power terminal to connect to the power line according to the
product specifications, and then connect to the signal line according to the required output signal. See
Table 2 for the specific meaning of the integrated electromagnetic flowmeter wiring terminals.
Table 2
Terminal Symbol
Function
1
T-/B
RS485/RS232 communication output
2
RS232 GND
RS232 grounding wire
3
T+/A
RS485/RS232 communication input
4
IOUT
4mA~20mA DC output;
Summary of Contents for MFE600C