background image

3

 

Operating Instructions

 

The flame simulator operation  is extremely simple. Once aligned, simply press the button, 
maintaining alignment, and wait for the detector to go into alarm. The flame simulator LED’s will 
flash when energised, and the detector response time should typically be less than 10 seconds.

 

The switch is spring loaded and releasing the pressure from the switch will disconnect the power.

 

Charging Socket inside end cap

 

Pushbutton

 

The picture above shows the FS301 flame simulator. The on/off pushbutton is shown to the 
underside of the flame simulator. The charging socket is on the reverse end from the faceplate 
window, inside the end cap. The FS301 flame simulator will operate for a maximum of 60 seconds

 

before timing out.

 

micropack.co.uk

 

 

 

FS301 Flame Simulator

 

FS301 Safety and Technical Manual

 

5

 

Ref: 2301.6042

 

Rev: 2.3 ECN: 4553

 

 

 

 

Summary of Contents for 2301.6042

Page 1: ...FS301 FLAME SIMULATOR SAFETY TECHNICAL MANUAL Ref 2301 6042 ECN 4431...

Page 2: ...E OF This document is strictly private and confidential reproduction without Micropack approval is prohibited Micropack Engineering Ltd 2015 FS301 Flame Simulator FS301 Safety and Technical Manual 2 R...

Page 3: ...attempt to replace the window as the glass and the front cover are individually matched pairs to meet the stringent requirement of the Hazardous area certification The threaded portions of the detecto...

Page 4: ...r is a portable hand held unit designed for single operator operation Robust and Reliable The flame simulator has been designed for extreme offshore conditions Reduced Maintenance Costs Reduces the ne...

Page 5: ...ng loaded and releasing the pressure from the switch will disconnect the power Charging Socket inside end cap Pushbutton The picture above shows the FS301 flame simulator The on off pushbutton is show...

Page 6: ...n on charger unit Wait until charger LED is green The yellow button causes the charger unit to completely discharge the battery pack prior to re charging Unless this is done the battery pack will reta...

Page 7: ...the flame simulator fails to operate there are two simple causes a b The flame simulator batteries need recharged or The unit is faulty and needs to be returned to Micropack 5 2 Replacement and Repai...

Page 8: ...RH 0 100 Non Condensing Parameter Units Value Comment Enclosure Overall Dimensions mm 100 Diameter x 200 Length Shipping Weight Kg 2 5 Material LM25 Alloy Coating Colour Red Epoxy Coated Finish Pushb...

Page 9: ...3 ECN 4553 Certification and Approvals Parameter Authority Standard Approval Certificate Hazardous Area Certification EN 60079 1 2014 Ex II 2 2 G Ex db op is T6 Gb IIC T6 Gb IP66 FM09ATEX0034 Explosi...

Page 10: ...056 Email info micropack co uk From Tel Fax Email I suggest the following corrections changes be made to Section Marked up copies attached as appropriate Yes No Please inform me of the outcome of this...

Page 11: ...4 0 1224 784056 Email sales micropack co uk micropack co uk In the Americas MICROPACK Detection Americas Inc 1227 Lakecrest Court Fort Collins Colorado 80526 Tel 1 970 377 2230 Fax 1 970 377 2273 Emai...

Reviews: