Micronor MR380-1-3 Instruction Manual Download Page 13

MR380-1-3 Instruction Manual 

Page 13 of 29 

 

4.

 

Troubleshooting 

 

The following are potential issues and recommended solutions when troubleshooting the MR380-

1-3 fiber optic system. For issues not listed, please contact Micronor Sales. 

 

 

Potential Issues & Solutions 

 

If the Instructions do not rectify the problem, then contact Micronor Sales for further assistance. 

 

Function 

Symptom 

Instructions 

‘Power’  

Green LED 

Not 

illuminated 
when 
controller 

powered 

 

Verify solid electrical connection between wires and screw 

terminal for both +24VDC and GND. 

 

Verify controller module power supply is +24VDC with a current 
output of at least 80mA. 

‘Emergency ON’ 
 Red LED 

 
(Using MR387 
Only) 

Illuminated 
when E-Stop 

not depressed 

 

Check if emergency switch is ‘On’ when depressed. If so, reset 
switch and verify ‘Emergency ON’ is now off. 

 

Verify optical link cabling is properly connected and undamaged. 

 

Verify that the  fiber optic system does not exceed system loss 
margin specifications. Measure the output power using a power 
meter set at 1300nm. It should read between -8.5dBm to -6.5dBm 

when  using  62.5/125µm  or  50/125µm  MM  fiber,  or    between            
-9.5dBm to -6.5dBm when using 9/125µm SM fiber. 

 

Clean all fiber optic connector surfaces using appropriate cleaning 

materials. 

+5V and +24V 
Digital Outputs 

No high 
voltage output 

 

Verify  solid electrical connection between wires and screw 
terminal for Digital Out and GND. 

 

Verify that the controller module is properly powered with 
+24VDC and grounded. 

 

Verify emergency switch is connected and 'Emergency ON’ is off. 

Relay 

Switching 
failure 

 

Verify solid electrical connection between wires and screw 
terminal for NO2, NC2, CM2, NO1, NC1, CM1 

 

Verify that the controller module is properly powered with 

+24VDC and grounded. 

 

Verify E-Stop Switch is connected and “Emergency ON’ is off. 

 

Verify when switch is depressed the controller will electro-
mechanically switch the state of the relay resulting in a faint ‘click’ 

sound. 

Damaged 
Sensor  

E-Stop 

 

Verify controller module outputs optical power by connecting LC 
loopback directly from one LC connector to the other, shown in 

Figure 9

. ‘Power’ should be illuminated and ‘Emergency ON’ 

should be OFF. 

 

Verify undamaged fiber with visual fault finder. 

 

Verify that the switch loss is less than the Optical Insertion Loss 

specification of the switch sensor using an optical power meter. 

 

Clean fiber optic surfaces on the switch using the appropriate 
cleaning materials. 

 

Summary of Contents for MR380-1-3

Page 1: ...43 4020 sales micronor ch www micronor ch Notice of Proprietary Rights The design concepts and engineering details embodied in this manual which are the property of MICRONOR LLC are to be maintained i...

Page 2: ...claration of Conformity D1 12 1 2016 Corrected SIL typo is SIL1 PLc D2 3 2 2017 Added Single Mode Declaration of Conformity to Appendix D3 5 18 2017 Remove 850nm Multimode Option D4 9 27 2019 Single M...

Page 3: ...Connections 11 3 4 2 MR380 1 3 and MR387 E Stop System Start Up Performance Check 12 4 Troubleshooting 13 Potential Issues Solutions 13 Damaged in Shipment 14 5 Warranty Information 15 6 Specification...

Page 4: ...ly Hierarchy of E Stop Switch 10 Figure 6 E Stop Switch Orientation Interchangeable when Mounting into Optical Block 10 Figure 7 Front Panel Outputs of MR380 1 3 Controller Error Bookmark not defined...

Page 5: ...location The entire fiber optic sensor system has a generous system loss budget enabling long distance systems complex routing and daisy chaining of multiple switches Depressing the switch interrupts...

Page 6: ...e signaling detection that can be deployed in difficult hazardous environments and over very long distances The Microswitch employs a photo interrupt scheme operating over a duplex 62 5 125 m fiber op...

Page 7: ...wo optical circuit configurations The Normally Open NO layout corresponds to an optical circuit that is open until the microswitch is depressed the Normally Closed NC layout corresponds to an optical...

Page 8: ...1 3 Controller Module MR380 1 3 Controller Module Phoenix Terminal Block 1879599 inserted as part of unit Instruction Manual this document one soft copy supplied with each shipment MR387 series Sensor...

Page 9: ...n LC Duplex optical cable is used to interconnect the sensor and controller The sensor incorporates a 3m optical pigtail or alternate length as specified by customer If a longer connection to the cont...

Page 10: ...cal Reference Drawing in Section 9 2 Refer to Figure 6 below for switch orientation Secure panel mount switch with all appropriate designations and requirements Figure 6 E Stop Switch Orientation Inte...

Page 11: ...a Phoenix Contact screw terminal For more information consult Controller specifications given in Section 6 1 If connectors are lost or damaged contact Micronor Sales for replacement details MR380 1 3...

Page 12: ...do so at this time and verify that the EMERGENCY ON LED red is as shown below E Stop Switch Power LED Emergency ON LED 24V Digital Out 5V Digital Out Relay Contacts Not Depressed ON OFF Hi 20V Hi 4V...

Page 13: ...or between 9 5dBm to 6 5dBm when using 9 125 m SM fiber Clean all fiber optic connector surfaces using appropriate cleaning materials 5V and 24V Digital Outputs No high voltage output Verify solid ele...

Page 14: ...ite or call your nearest MICRONOR office in the U S A Please retain the shipping container in case reshipment is required for any reason If you receive a damaged instrument you should 1 Report the dam...

Page 15: ...Repaired products are warranted for the balance of the original warranty period or at least 90 days Limitations of Warranty This warranty does not apply to defects resulting from unauthorized modific...

Page 16: ...le Mode OS1 9 125 or SMF 28 System Loss Budget Minimum 23dB Typical 25dB Maximum Optical Link Length Distance is a function of user s system loss budget which is the total round trip loss of all optic...

Page 17: ...Relay NO contacts Closed Functional Safety For MR387 E Stop Sensor MR380 1 3 Universal Controller ISO 13849 Category 2 MTTFd 4 14 E 06 hours 473 1 years Performance Level PL c Safety Integrity Level...

Page 18: ...g IP65 Mechanical Housing Aluminum body anodized finish Durability 100 000 operations min Physical Housing Dimension Consult Mechanical Reference Drawing Mounting Consult Mechanical Reference Drawing...

Page 19: ...the receiving fiber is only slightly smaller than the transmitting fiber there is a smaller loss that can be built into the system loss budget For example transmitting from OM1 fiber 62 5 m core to O...

Page 20: ...tem The light source power is held constant under normal operating conditions allowing for a known system loss budget when designing a system Additionally the optics within the switch are designed to...

Page 21: ...series permitted that the additional losses fall within the optical system loss budget Figure 11 illustrates a system using three MR387 switches in series For more information on System Loss Budget pl...

Page 22: ...ll additional losses fall within the optical system loss budget This allows a single E stop to control multiple systems or switch off multiple sources of energy even if large distances separate the sy...

Page 23: ...ual Page 23 of 29 9 Reference Documents See following pages for these reference drawings and documents MR380 1 Controller Reference Drawing MR387 E Stop Reference Drawing 2 pages MR380 Series Declarat...

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ...Page 1 of 19...

Page 28: ...Page 2 of 19...

Page 29: ...Page 3 of 19...

Reviews: