-6-
Tubing Size
Standard tubing
Length (m)
Max tubing
Length (m)
Height
Difference (m)
Additional
refrigerants(g/.m)
Narrow (mm)
Wide (mm)
φ
6.35(1/4”)
φ
9.52(3/8”)
3.5
9
5
15
φ
6.35(1/4”)
φ
12.7(1/2”)
3.5
12
7
15
φ
6.35(1/4”)
φ1
5.88(5/8”)
4
15
8
15
φ
9.52(3/8”)
φ1
5.88(5/8”)
4
15
8
15
〖
Fixing Installation Panel
〗
Dismantle the metal installation board of the indoor unit. Adjust the mounting panel to horizontal position.
Drill holes and insert plastic expansion tubes at the appropriate locations on the wall and fix the installation
board on the wall with M5x30 screws and washer 6. Ensure that there must be at least 4 fixed points in the
wall. Ensure installation board to horizontal position.
Drill holes as Fig. 4 shows. The hole, 80mm in diameter, should slightly slide down outwards...
Cut PVC tubes at a slight angle in the length shorter than wall thickness and inset it into the hole.(
Fig.5
)
Mount the wall cap.
Left side
Right side
Wall cap
Wall
PVC tube
Small angle
Fig.5
Left
Right
Left
Right
Horizontal direction
Horizontal direction
Notes:
Left chart is available for the position of drain hose, refer to Fig.7.
Right chart is available for the position of drain hose, refer to Fig.9.