PAGE 23
© 2021 OJ Electronics A/S
Power limit (
PLi
) 2/2
Enter 6 minutes in the power limit menu in order to reduce
the heating by 10%
Equation to calculate number of minutes that could
be entered in the power limit menu - when an average
heating effect is desired:
Average desired heating effect per m
2
Floor heating element output per m
2
(
1-
(
)
)
∗
60 min
Note:
If the result of the equation is negative then nothing
should be entered.
The function is factory set to 0 minutes but can be set to
values between 0-30 minutes in steps of 1 minute
Menu structure:
PLi
: 0 30min
REMOTE