7
Zone Controller Installation
3.3
Mechanical installation of the Zone Controller
To surface mount the Zone Controller enclosure
1. Remove the front door and disconnect the bonding strap.
Figure 3
Mechanical installation of the Zone Controller
2. Remove the four screws securing the inner chassis to the backbox and remove the inner
chassis.
3. Mark the location of the four mounting holes of the backbox on the wall. Drill the holes
and use any additional anchoring devices. For example, dry wall or cement plugs.
4. Fasten two screws halfway into the wall in the top two positions marked in step 3, using
#6 screws.
5. Remove knockouts and attach conduit.
6. Hang the box onto the two screws.
7. Screw the other two screws at the bottom of the backbox
8. Tighten all four screws into place.
9. Once wiring is complete, mount the inner chassis and front door, making sure to
reconnect the bonding strap to the front door.
3.4
Conduits for Wiring
AC power must be run through a dedicated conduit. Use the bottom left conduit for AC wiring.
Use the top left conduit for input wiring and the top right for output wiring. Refer to Figure 3.
FRONT DOOR
INNER CHASSIS
Bonding
Strap
Conduit for
Inputs
Lift Antenna
once installed
Conduit for
Outputs
Conduit for
AC Power
BACKBOX
Summary of Contents for Fire-Link 3