MICROIDEA EPFCB Installation Manual Download Page 11

 

11 / 16 

 

- ITALY - Tel. +39.035.773 925 - Fax +39.035.773 933 - e-mail: [email protected] - Web: www.microidea.it 

ALARM MENU (DEFAULT): 

Description 

Threshold 

Time 

hh:mm:ss 

Alarm Relay 

Steps

 

 Too high voltage 

10% 

00:15:00 

ON 

ON 

 Too low voltage 

15% 

00:00:05 

ON 

OFF 

 Too high current 

110% 

00:02:00 

ON 

OFF 

 Too low current 

2.5% 

00:00:05 

ON 

ON (00:02:00) 

 Overcompensation 

ON 

00:02:00 

ON 

OFF 

 Undercompensation 

ON 

00:15:00 

ON 

OFF 

 Overtemperature 

45°C 

00:00:10 

ON 

OFF 

 THD V  

OFF 

00:00:00 

ON 

OFF 

 THD I 

OFF 

00:00:00 

ON 

OFF 

 Too low Cos

j

  

OFF 

00:01:00 

ON 

OFF 

 External overtemperature 

OFF 

00:00:10 

ON 

OFF 

 Capacitors overload 

(1)

 

Thresh.1 = 125% 

00:03:00 

ON (00:05:00) 

Thresh.2 = 150% 

 No-Voltage release 

(2)

 

ON 

OFF 

ON 

Alarm page sample with the maximum configurable options: 

 
 

 
 
 
 
 
 
 
 
 
 
 

 

 

 

(1)  The delay time of Capacitor overload alarm operates inversely proportional to the overload entity, compared to the 

programmed thresholds of Thresh.1 and Thresh.2. 

When the overload is lower than Thresh.1 the alarm will not be generated. 

When the overload is equal to Thresh.1, the delay time is equal to the one set. 

When the overload increases, the delay time decreases proportionally until it reaches zero once the value set at 
Thresh.2 is reached. 

With  Thresh.1 at off , there is no tripping until the Thresh.2 value is exceeded and the immediate disconnection of 
the steps occurs. 

With Thresh.2 at off , the delay time is constant. 

Protection is performed through the Steps disconnection and Alarm relay enabling ( if ON ). 

The alarm is deactivated only after the value has dropped and stay costantly below the settled threshold for all the 
Alarm relay-off delay time set. Now the steps are reconnected and the system will work as usual. 

Note: 

This protection can only be used if the capacitors are not equipped with filtering devices such as inductors or similar. 

(2)  A no-voltage release has occurred on the line voltage inputs for more than 9ms. 

Threshold % or status 

Alarm relay status  

Step disconnection status 

Threshold delay 

Step disconnection delay 

Alarm relay-off delay 

Summary of Contents for EPFCB

Page 1: ...e asupra dispozitivului ndep rta i toate tensiunile de la intr rile de m surare i de alimentare i scurtcircuita i bornele de intrare CT Produc torul nu poate fi considerat responsabil pentru siguran a...

Page 2: ...connection device See note in the box in the upper right corner of the wiring diagrams The value has to be calculated according to the VT used NOTE The transformer VT is used To isolate the controller...

Page 3: ...onnection type Press to go to voltage value Use to set the desired value Press to save and exit Press to discard and go back to the previous page Now the instrument shows the home page with the system...

Page 4: ...he instrument to follow precisely the settled Cosj Press for 1s to switch between modes IMPORTANT it s possible to access the settings menu only in MAN mode Capacitors overload value Step config visua...

Page 5: ...SETTINGS ALARMS If no key is pressed for 30s the instrument goes back to the home page unless the instrument is into a config page In this case a timeout is configurable by using A 11 parameter When t...

Page 6: ...of function of the keys return to menu increase the value or change the data decrease the value or change the data go to the next parameter In the intermediate pages press go to previous parameter if...

Page 7: ...Web www microidea it Now press to go back to the settings menu If you have changed the values or settings when prompted to save press to confirm or to cancel Press again to return to navigation pages...

Page 8: ...ated respectively the voltage and current THD distorsion by the use of vertical bars for each harmonic up to the 30th Press to show details of the single harmonics use to scroll page GRAPHS This is a...

Page 9: ...are indicated INFO STEP This page shows details of configurations and working cycles of every configured and connected step A Step number B Nominal reactive power C Working hours D Insertion number Pr...

Page 10: ...ase L1 DIRECT REVERSE L2 DIRECT REVERSE L3 DIRECT REVERSE L1 DIRECT A 03 Frequency Hz 50 60 50 Hz A 04 Data communication Type RS485 ETHERNET RS485 A 05 RS485 Address DISABLED 1 199 1 n Protocol MODBU...

Page 11: ...the overload is lower than Thresh 1 the alarm will not be generated When the overload is equal to Thresh 1 the delay time is equal to the one set When the overload increases the delay time decreases p...

Page 12: ...e access to all menu items will remain active for 5m To deactivate the password enter the value 00000 and save SETTING STEPS You can set the steps manually or perform automatic acquisition In the Sett...

Page 13: ...to the parameter list of the Advanced Menu 6 Press and release when prompted to save press to confirm or to cancel 7 The device will restart and will be possible to communicate in RS485 with the set...

Page 14: ...ed voltage 250V Maximum current at contact common 10A C1 C2 8A 13 14 Insulating category Rated voltage VDE0110 C 250 B 400 Electrical contact Life 20 x 1006 ops Mechanical contact Life 100 x 103 ops A...

Page 15: ...15 16 ITALY Tel 39 035 773 925 Fax 39 035 773 933 e mail microidea microidea it Web www microidea it BACK PANEL CONNECTIONS DIMENSIONS FRONT VIEW SIDE VIEW MOUNTING HOLE...

Reviews: