background image

 

 

MM30-W

 

Doc. N° MO-0117-ING 

Rev. 

1

 

Pag. 

17  

of 

29

 

 

Copyright - 2010 -  Microener

 

 

13. MANUAL TEST OPERATION 

 

13.1 - Mode "TESTPROG" subprogram "W/O TRIP" 

 

Operation of the yellow key activates a complete test of the electronics and the process routines.  
All the leds are lit-on and the display shows (TEST RUN).   If the test routine is successfully 
completed the display switches-over to the default reading (xx:xx:xx). 
If an internal fault is detected, the display shows the fault identification code and the relay R5 is 
deenergized.  This test can be carried-out even during the operation of the relay without affecting the 
relay tripping in case a fault takes place during the test itself. 

 

13.2 - Mode "TESTPROG" subprogram "WithTRIP" 

 

 

Access to this program  is enabled only if the current detected is zero (breaker open). 
Pressing the yellow key the display shows "TEST RUN?". A second operation of the yellow key starts 
a complete test which also includes the activation of all the output relays. 
The display shows (TEST RUN) with the same procedure as for the test with W/O TRIP. 
Every 15 min during the normal operation the relay automatically initiates an auto test procedure 
(duration 

 10ms). If any internal fault is detected during the auto test, the relay R5 is deenergized, 

the relevant led is activated and the fault code is displayed. 

 

 

WARNING 

 

 

Running the 

WithTRIP

 test will operate all of the output relays. Care must be taken to ensure that no 

unexpected or harmful equipment operations will occur as a result of running this test. 
It is generally recommended that this test be run only in a bench test environment or after all 
dangerous output connections are removed. 

 

14. MAINTENANCE 

 

No maintenance is required. Periodically a functional check-out can be made with the test procedures 
described under  MANUAL TEST chapter. In case of malfunctioning please contact   
Microelettrica Scientifica Service or the local Authorised Dealer mentioning the relay's Serial No reported 
in the label on relays enclosure. 

 

 

WARNING 

 

 

In case of Internal Relay Fault detection, proceed as here-below indicated : 

 

 

If the error mes

sage displayed is one of the following “DSP Err”, “ALU Err” ,”KBD Err” ,”ADC Err”, 

switch off power supply and switch-on again. If the message does not disappear send the relay to 
Microelettrica Scientifica (or its local dealer) for repair. 

 

If the error me

ssage displayed is “E2P Err”, try to program any parameter and then run “W/OTRIP”.  

 

If message disappear please check all the parameters.  

 

If message remains send the relay to Microelettrica Scientifica (or its local dealer) for repair. 

 

15. POWER FREQUENCY INSULATION TEST 

 

Every relay individually undergoes a factory insulation test according to IEC255-5 standard at  
2 kV, 50 Hz 1min. Insulation test should not be repeated as it unusefully stresses the dielectrics.  
When doing the insulation test, the terminals relevant to serial output must always be short circuited to 
ground.  When relays are mounted in switchboards or relay boards that have to undergo the insulation 
tests, the relay modules must be drawn-out of their enclosures and the test must only include the fixed 
part of the relay with its terminals and the relevant connections. 
This is extremely important as discharges eventually tacking place in other parts or components of the 
board can severely damage the relays or cause damages, not immediately evident to the electronic 
components. 

Summary of Contents for MM30-W

Page 1: ...ght 2010 Microener MICROPROCESSOR MOTOR PROTECTION RELAY TYPE MM30 W OPERATION MANUAL MULTIFUNCTION MOTOR PROTECTION RELAY TYPE MM30 W ENTER RESET MODE SELECT PROG St N I O PROG I R F MICROELETTRICA S...

Page 2: ...___________________________________ 10 9 Keyboard and display operation_________________________________________________________ 11 10 Reading of measurements and recorded parameters__________________...

Page 3: ...compatible with their declared performance 1 6 PROTECTION EARTHING When earthing is required carefully check its effectiveness 1 7 SETTING AND CALIBRATION Carefully check the proper setting of the dif...

Page 4: ...s should not be altered or replaced For repair please ask the Manufacturer or its authorised Dealers Misapplication of the above warnings and instruction relieves the Manufacturer of any liability 2 G...

Page 5: ...displayed with one of the groups of digits YY MMM or DD blinking The DOWN key operates as a cursor It moves through the groups of digits in the sequence YY MMM DD YY The UP key allows the user to modi...

Page 6: ...ning by the key SELECT Parameter modification by the key Set validation by the key ENTER Scanning of the menus by the key MODE SELECT ENTER Enabled only if input current is zero ENTER RESET MODE SELEC...

Page 7: ...Illuminated on tripping of the unbalance inverse time element tI2 or of the single phasing element 1 e Yellow LED PROG I R F Flashing during the programming of the parameters Illuminated on Internal R...

Page 8: ...herebelow The module REX 8 includes eight RA RB RC RD RE RF RH RG user programmable plus one R Diag diagnostic output relays The master module MM30 W can control altogether up to sixteen output relays...

Page 9: ...can be connected via a cable bus a fiber optic bus for interfacing with a Personal Computer type IBM or compatible All the functionalities that can be operated locally for example reading of input me...

Page 10: ...RTD ON see 12 1 If the function is enabled the input RTD is activated when the resistance connected to the terminals 1 14 exceeds the limits 50 R1 14 2900 This limits respectively correspond to Short...

Page 11: ...memory SET DISP Reading of the settings and of the configuration of the output relays as programmed PROG Access to the programming of the settings and of relay configuration TEST PROG Access to the ma...

Page 12: ...xxxV RMS Voltage displayed as primary volts 0 65000 fxx xxHz Frequency 40 70 Hz PFx xxC Power Factor 0 10 1 00 C Lead L Lag xxx Phase displacement WxxxxxKW Active Power 0 10000 kW h xxxxx Operation ho...

Page 13: ...rent T Tnxxx Motor heating Uxx xxUn Phase to phase voltage fxx xxHz Frequency PFx xxC Power Factor 0 00 1 00 C Lead L Lag 10 4 TRIP NUM Counters of the number of operations for each of the relay funct...

Page 14: ...to speed up parameter s variation press the key SELECT while or are pressed Press key ENTER RESET to validate the set values 12 1 PROGRAMMING OF FUNCTIONS SETTINGS Mode PROG menu SETTINGS Production s...

Page 15: ...1 5 0 1 Ist tI 0 1s Trip time delay of phase overcurrent element 0 05 1 0 01 s O 0 1On Trip level of earth fault element Dis 0 02 2 0 01 On tO 0 2s Trip time delay of earth fault element 0 05 5 0 01...

Page 16: ...perates relay R1 R2 R3 R4 RA RB RL I No load running tripping operates relay R1 R2 R3 R4 RA RB RL I Instantaneous overcurrent tripping operates relay R1 R2 R3 R4 RA RB RL tI 2 Time delayed overcurrent...

Page 17: ...ment or after all dangerous output connections are removed 14 MAINTENANCE No maintenance is required Periodically a functional check out can be made with the test procedures described under MANUAL TES...

Page 18: ...MM30 W Doc N MO 0117 ING Rev 1 Pag 18 of 29 Copyright 2010 Microener...

Page 19: ...ed oscillatory magnetic field IEC61000 4 10 100A m 0 1 1MHz Electrical fast transient burst IEC61000 4 4 level 3 2kV 5kHz HF disturbance test with damped oscillatory wave 1MHz burst test IEC60255 22 1...

Page 20: ...MM30 W Doc N MO 0117 ING Rev 1 Pag 20 of 29 Copyright 2010 Microener The performances and the characteristics reported in this manual are not binding and can modified at any moment without notice...

Page 21: ...MM30 W Doc N MO 0117 ING Rev 1 Pag 21 of 29 Copyright 2010 Microener 17 CONNECTION DIAGRAM SCE1630 Rev 0 Standard Output 17 1 CONNECTION DIAGRAM SCE1667 Rev 0 Double Output...

Page 22: ...of 29 Copyright 2010 Microener 18 WIRING THE SERIAL COMMUNICATION BUS SCE1309 Rev 0 19 CHANGE PHASE CURRENT RATED INPUT 1 OR 5A J1 Phase A J2 Phase C J4 Neutral Rated Input Current Rated Input Current...

Page 23: ...MM30 W Doc N MO 0117 ING Rev 1 Pag 23 of 29 Copyright 2010 Microener 20 THERMAL IMAGE CURVES TU0249 Rev 1...

Page 24: ...IME UNBALANCE PROTECTION ELEMENT TU0248 Rev 1 tI2 I2 Im tI2 0 1 I2 Im 0 9 t I2 Im Comp sequenza neg Negative sequence comp I2 Im Soglia minima di funzionamento Minimum operation level tI2 Ritardo inte...

Page 25: ...of the screws driver mark Draw out the PCB by pulling on the handle 22 2 Plug in Rotate clockwise the screws and in the horizontal position of the screws driver mark Slide in the card on the rails pro...

Page 26: ...MM30 W Doc N MO 0117 ING Rev 1 Pag 26 of 29 Copyright 2010 Microener 23 OVERALL DIMENSIONS MOUNTING PANEL CUT OUT 113x142 LxH View of Rear Terminal Connection...

Page 27: ...xxV NodAdxxx 23 to tm xxx tm xxmin Autoset tTr xxxs ITrxxxIst tst xxxs tBst xxm tStNoxxm tI2 xs I2 xxxIm Ts n xxx Ta n xxx 22 19 18 17 25 24 26 21 20 I xxxIst I xxxIm tLR xxs ILRxxxIm 32 31 30 29 28 2...

Page 28: ...ime after tripping of the function StNo 1 60 Rm m 12 ILR Trip level of Locked Rotor function Dis 1 5 Im 2 tLR Trip time delay of LR element during run 1 25 s 5 I2 Trip level of inverse time current un...

Page 29: ...No load running tripping operates relay I I Instantaneous overcurrent tripping operates relay I tI 2 Time delayed overcurrent tripping operates relay tI O Instantaneous earth fault tripping operates...

Reviews: