12.2 - PROGRAMMING THE CONFIGURATION OF OUTPUT RELAYS
Mode PROG menu F
RELAY (Settings out of production are here under shown).
The key "
+
" operates as cursor; it moves through the digits corresponding to the four relays programmable for any
functions in the sequence 4-3-2-1-L-K-J-I-H-G-F-E-D-C-B-A (4=Relay R4 etc.) and makes start flashing the
information actually present in the digit. The information present in the digit can be either the number/letter of the
relay (if this was already associated to the function actually on programming) or a dot (-) if this place was not yet
addressed.
Display
Description
Only for Version
MM30-DKX
T>
---1
Overload tripping
operates relay R1, R2, R3, R4
RA,RB
RL
Ta
----
Overload prealarm tripping
operates relay R1, R2, R3, R4
RA,RB
RL
ITr
----
Starting switch-over tripping
operates relay R1, R2, R3, R4
RA,RB
RL
StNo
---1
Start No limitation tripping
operates relay R1, R2, R3, R4
RA,RB
RL
ILR
---1
Locked Rotor tripping
operates relay R1, R2, R3, R4
RA,RB
RL
tI2>
---1
Time delayed unbalance tripping
operates relay R1, R2, R3, R4
RA,RB
RL
I<
----
No load running tripping
operates relay R1, R2, R3, R4
RA,RB
RL
I>
----
Instantaneous overcurrent tripping
operates relay R1, R2, R3, R4
RA,RB
RL
tI>
---2
Time delayed overcurrent tripping
operates relay R1, R2, R3, R4
RA,RB
RL
O>
----
Instantaneous earth fault tripping
operates relay R1, R2, R3, R4
RA,RB
RL
tO>
---2
Time delayed earth fault tripping
operates relay R1, R2, R3, R4
RA,RB
RL
RT
----
Remote trip command (input 1-2)
operates relay R1, R2, R3, R4
RA,RB
RL
1
---1
Time delayed Phase loss tripping
operates relay R1, R2, R3, R4
RA,RB
RL
I>
- 2 - 4
This dash means
that output relay
number 1 is not
assigned to this
element
This is the name of
protective element
The number 2
means that
output relay 2 will
operate when
this
element trips
This dash means
that output relay
number 3 is not
assigned to this
element
The number 4 means
that output relay 4 will
operate when this
element trips