MC30-R2
Doc. N°
MO-0462-ING
Copyright 2012
FW: 1290.37.01.x
Date
06.09.2022
Rev.
1
Pag.
27
of
38
12. MENU AND VARIABLES
12.1 - Real Time Measurements
Scrolling display of the Real Time Measurements is the Default operation.
Scrolling can be stopped at any of the measurements and restarted by pressing the Reset button
.
When stopped on one variable,
appears aside the measurement and the different available measurements
can be selected by the
buttons.
Display
Description
I
= 0
–
65535
%In
Largest of the 3 phase-currents (% of rated current)
IA
= 0
–
65535
A
RMS value of Phase A current
IB
= 0
–
65535
A
RMS value of Phase B current
IC
= 0
–
65535
A
RMS value of Phase C current
Io
= 0.0
–
6553.5
A
RMS value of Zero Sequence Current (RMS Primary Amps)
Tem
= 0 - 65535
%T
Actual temperature rise
12.2 - Measure (Instantaneous Measurements)
Real time measurements can be frozen at
any moment selecting the menu “Instant Measure”
:
“
R
eal
T
ime
M
eas”
“Measure”
“1
st
Measurement
other measurements
to go back to “ Measure”
Display
Description
I
= 0
–
65535
%In
Largest of the 3 phase-currents (% of rated current)
IA
= 0
–
65535
A
RMS value of Phase A current
IB
= 0
–
65535
A
RMS value of Phase B current
IC
= 0
–
65535
A
RMS value of Phase C current
Io
= 0.0
–
6553.5
A
RMS value of Zero Sequence Current (RMS Primary Amps)
Tem
= 0 - 65535
%T
Actual temperature rise
12.3 - Counter (Operation Counters)
The operation of any of the function herebelow reported, is counted and recorded in the menu
“
Counters
”
.
“
R
eal
T
ime
M
eas”
“Counter”
“
1
st
counters
”
other counters
to go back to “Counter”
Display
Description
T>
=
0
–
65535
Number of Thermal Image
I>
=
0
–
65535
Number of 1
st
Overcurrent (time delayed) trip
I>>
=
0
–
65535
Number of 2
nd
Overcurrent (time delayed) trip
IH
=
0
–
65535
Number of 3
rd
Overcurrent (time delayed) trip
Io>
=
0
–
65535
Number of 1
st
time delayed Earth Fault trip
Io>>
=
0
–
65535
Number of 2
nd
time delayed Earth Fault trip
IoH
=
0
–
65535
Number of 3
rd
time delayed Earth Fault trip
BF
=
0
–
65535
Number of operation of Breaker Failure
I.R.F.
=
0
–
65535
Number of Internal Relay Faults
RCL1
=
0
–
65535
Number of first Reclosure
RCL2
=
0
–
65535
Number of 2
nd
Reclosure
RCL3
=
0
–
65535
Number of 3
rd
Reclosure
RCL4
=
0
–
65535
Number of 4
th
Reclosure
RCLF
=
0
–
65535
Number of failed Reclosure
HR
=
0
–
65535
Number of HW recovery operations