3.6 - Io>> (2F51N) - Second Earth Fault protection level
FuncEnab
→
Enable
[Disable / Enable]
Options
→
BI
Disable
[Disable / Enable]
→
Trg
Enable
[Disable / Enable]
→
Sh1
No
[No / Yes]
→
Sh2
No
[No / Yes]
→
Sh3
No
[No / Yes]
→
Sh4
No
[No / Yes]
TripLev
→
Io>>
0.01
Ion (0.01
9.99)
step 0.01
Ion
Timers
→
tIo>>
0.05
s
(0.05
60.00)
step
0.01
s
Description of variables
FuncEnab
: If disable the function is disactivated
BI
: Operation controlled by Blocking Digital Input
Trg
: Function operation triggers the oscillographic wave form capture
(see § Oscillographic Recording)
Sh1
: Tripping of this function (2F51N) starts (Yes) or not (No) the first reclosure shot.
Sh2
: Tripping of this function (2F51N) starts (Yes) or not (No) the 2
nd
reclosure shot.
Sh3
: Tripping of this function (2F51N) starts (Yes) or not (No) the 3
rd
reclosure shot.
Sh4
: Tripping of this function (2F51N) starts (Yes) or not (No) the 4
th
reclosure shot.
Io>>
: Minimum Zero Sequence Residual Current Pick-up level
tIo>>
: Trip time delay
3.7 - IoH (3F51N) - Third Earth Fault protection level
FuncEnab
→
Enable
[Disable / Enable]
Options
→
BI
Disable
[Disable / Enable]
→
Trg
Enable
[Disable / Enable]
→
Sh1
No
[No / Yes]
→
Sh2
No
[No / Yes]
→
Sh3
No
[No / Yes]
→
Sh4
No
[No / Yes]
TripLev
→
IoH
0.01
Ion (0.01
9.99)
step 0.01
Ion
Timers
→
tIoH
0.05
s
(0.05
60.00)
step
0.01
s
Description of variables
FuncEnab
: If disable the function is disactivated
BI
: Operation controlled by Blocking Digital Input
Trg
: Function operation triggers the oscillographic wave form capture
(see § Oscillographic Recording)
Sh1
: Tripping of this function (3F51N) starts (Yes) or not (No) the first reclosure shot.
Sh2
: Tripping of this function (3F51N) starts (Yes) or not (No) the 2
nd
reclosure shot.
Sh3
: Tripping of this function (3F51N) starts (Yes) or not (No) the 3
rd
reclosure shot.
Sh4
: Tripping of this function (3F51N) starts (Yes) or not (No) the 4
th
reclosure shot.
IoH
: Minimum Zero Sequence Residual Current Pick-up level