12
http://www.microcyber-fieldbus.com
HART DIN Rail Temperature Transmitter | NCS TT106H R1 | Page
Email | [email protected]
temperature.
R0 Correction Factor: Correction of the error of the sensor
itself (range 0.9-1.1).
Two-wire zero calibration: When the
temperature
transmitter is connected to RTD in 2-wire mode,to avoid
the error caused by the resistance on the cable, the sensor
end can be short connected, and then the zero calibration
button can be executed to eliminate the error caused by
the resistance on the cable.
TC Calibration: Calibration of various thermocouple ranges of
transmitters is carried out in the factory (only applicable to
manufacturer-level users).
RTD calibration: All kinds of resistance ranges of transmitter
are calibrated out of the factory (only for manufacturer-
level users).
。
Restore factory default value: Click this button, all data will
be restored to the default factory status.
Save as factory value: Click this button to save the current
configuration as factory value. When you click the “Restore
factory settings” button again, the saved configuration will
be restored.
Restore factory settings: Click this button to restore data to
factory status. If the user has saved the factory value, the
configuration saved by the user will be restored; otherwise,
the default factory status will be restored.
⚫
Current Calibration
The current calibration steps are as follow: