11
http://www.microcyber-fieldbus.com
HART DIN Rail Temperature Transmitter | NCS TT106H R1 | Page
Email | [email protected]
B_TC
B thermocouple
E_TC
E thermocouple
J_TC
J thermocouple
K_TC
K thermocouple
N_TC
N thermocouple
R_TC
R thermocouple
S_TC
S thermocouple
T_TC
T thermocouple
Wiring system
:
It can be set to 2-wire system, 3-wire system
and 4-wire system, only effective for RTD.
Cold-end temperature compensation: it can be set to prohibit,
internal measurement and external measurement. When
the cold-end temperature compensation is prohibited, the
transmitter will not carry out the cold-end temperature
compensation;
when
the
cold-end
temperature
compensation is enabled to measure internally, the value
of the cold-end temperature compensation is measured by
the internal temperature measuring chip; when the cold-
end temperature compensation is enabled to measure
externally, the external two-wire system Pt100 is used, and
then the value of the cold-end temperature compensation
is measured by the external Pt100.
Channel status: Display sensor channel status (open circuit,
short circuit & etc.).
Sensor channel value: Display the original value of sensor
channel.
Cold end temperature: Display the current cold end