PAGE 11
© 2016 OJ Electronics A/S
ADJ : Adjust
This option allows you to calibrate the measured room
temperature .
You should calibrate the sensor if the temperature reading
differs from the actual temperature .
The measured temperature has to be entered .
Note that with sensor application
F
, the temperature is
measured in the floor, this temperature would be higher
than the ambient temperature .
Adjust is not applicable if the sensor application is set
to
C
.
How to execute it:
You can calibrate the sensor with +/- 10°C in steps of
0 .1°C as follows:
• Access the menu .
• Scroll through the menu to ADJ .
• Press the centre button .
• Use the upper or lower button to adjust the sensor to
the value by which you want to increase/decrease the
temperature .
• Confirm your choice with the centre button .
Menu structure:
AdJ:
Measured tempe/- 10°C Factory: 0 .0°C