Mianyang Weibo Electronic WBV332S01 User Manual Download Page 5

 

5

Instruction of Installation and Use 

1. The product has adopted structure compliance with EN50022; suitable for DIN rail 

mounting NS35/7.5, NS35/15. Installation steps are as following (please reference to 
dimensional drawing):   

Step 1: Immobilize one side of product‘s mounting trough to the DIN mounting rail; 
Step 2: Pull out the spring clasp; 
Step 3: Place whole mounting trough to the DIN mounting rail properly; 
Step 4: Release spring clasp to make sure the installation.   

2.

 

The product has calibrated before out of factory. After correctly wiring, it can be 
powered and used immediately. But for further precise signal sampling, user needs to 
warm-up the product for 3 minutes before use. 

a)

 

The auxiliary power requires isolation voltage

2000V

AC

, DC current output ripple

10mV, and multiple converters can share with one set auxiliary power together.   

b)

 

When measuring dc voltage exceeds 500 volts, the circuit needs adding a resistor to 
divide the input dc voltage. The resistor is provided by Mianyang weibo Electronic, 
and only for each type of transducers special use only. 

 

 
 

Transducer 

V

Resistor 

 
 
 
 

 

3.

 

Basic testing method for accuracy 

(1)

 

According to the terminal definition table to connect the testing circuit; 

(2)

 

The testing must to be done by under the following conditions

 

Auxiliary power: 

24V

±

1

%,

ripple

5mV

 

Ambient temperature: 

25

℃±

2

 

Relative humidity

: RH(45

75)

 

Accuracy for Signal Power Source instrument: 

0.05 

 

 

 

 

Mianyang Weibo Electronic Co.,Ltd 

No.7 Road 2 of Xianren Road Youxian District Mianyang City P.R. China     

Tel: 86-816-2971265 Fax: 86-816-2281934 

www.wb-my.com

5

     

[email protected]

 

 

Summary of Contents for WBV332S01

Page 1: ...nsducer www wb my com wblch wbdz cn Technical Service 86 816 2278271 Quality Complain 86 816 2278273 Fax Line 86 816 2281934 ISO9001 ISO14000 GB T2800 CE Certified Quality Warranty Any quality problem found in WB series products we offer Three years free charge of repair the products and six months guaranteed free charge of change and return the products ...

Page 2: ...ceivable circumstances or include detailed information on all topics In the event of questions or specific problem do not take any action without proper authorization Contact the appropriate WB technical sales office and request the necessary information Standard application 1 Accuracy Accurate degree is conformed to IEC688 1992 2 Safety 2 1 Overload capability Overload capability is conformed to ...

Page 3: ...pure or pulsating voltage into a load independent output signal DC voltage 0 5V or 0 10V It has adopted modulation demodulation isolation principle and average measurement method for real time measurement of DC voltage from electric net The product has certain advantages of total galvanic isolation between input output high accuracy low drifting by temperature and wide temperature bearable range e...

Page 4: ...1MΩ 5 Linear Range 0 120 of nominal input 6 Responding Time 150ms 7 Over Load Capacity 2 times of nominal input continuous 8 Output current 5mA 9 Auxiliary Power 12Vdc 24Vdc 10 Current consumption for static status 10mA 11 Isolation Voltage 2500Vdc for 1 minute 12 Output Ripple 10mV 13 Drifting by Temperature 0 50 100 10 6 14 Ambient Temperature 10 50 15 Mounting DIN Rail 35mm Mounting or screw mo...

Page 5: ... auxiliary power requires isolation voltage 2000VAC DC current output ripple 10mV and multiple converters can share with one set auxiliary power together b When measuring dc voltage exceeds 500 volts the circuit needs adding a resistor to divide the input dc voltage The resistor is provided by Mianyang weibo Electronic and only for each type of transducers special use only 4 Transducer VX 6 Resist...

Page 6: ...transducer it shows the transducer s accurate grade is qualified Caution 1 Pay attention to the auxiliary power information especially the auxiliary power grade and polarity other wise will damage the product 2 Pay attention to the wire connection wrong terminal connection will cause malfunction of the product and even damage the product 3 Don t dismantle the product and carry with care to avoidin...

Page 7: ...s fire prevent ABS crust its temperature withstand is only limited as 85 higher than this limitation will cause the product deformation Please use and store carefully 8 This product can t be used to measure the pulse DC voltage signal otherwise there will be more errors or no output Mianyang Weibo Electronic Co Ltd No 7 Road 2 of Xianren Road Youxian District Mianyang City P R China Tel 86 816 297...

Reviews: