Mianyang Weibo Electronic WBV332S01 User Manual Download Page 2

 

2

 

WBV332S01 DC Voltage Transducer 

Safety claim 

The information in the safety claim of the equipment documentation is intended to ensure that 
equipment is properly installed in order to maintain it in a condition. 
It is assumed that everyone who would be associated with the equipment should be familiar with 
the contents of that safety section, or this safety guide. 
When electrical equipment is in operation, dangerous voltages will be present in certain parts of 
the equipment (e.g. the input terminal). Failure to obverse warning notices, incorrect use, or 
improper use may endanger personnel and equipment and course personal injury or physical 
damage. 
Before working in the terminal strip area, the equipment must be isolated. 
Proper and safe operation of the equipment depends on appropriate shipping and handling, proper 
storage, installation and commissioning, and on careful operation, maintenance and servicing. 
The operating manual for the equipment gives instructions for its installation, commissioning, and 
operation. However, the manual cannot cover all conceivable circumstances or include detailed 
information on all topics. In the event of questions or specific problem, do not take any action 
without proper authorization. Contact the appropriate WB technical sales office and request the 
necessary information.   
 

Standard application 

1. Accuracy 

    Accurate degree is conformed to IEC688:1992 

2. Safety 

  2.1 Overload capability 
        Overload capability is conformed to IEC688:1992 
 2.2 Isolation voltage 
        Can be endured testing voltage is conformed to Q/72085584-0.1-2004 
  2.3 Insulation impedance 
    The insulation impedance is no less than 20M Ohm, is conformed to 

Q/72085584-0.1-2004   

3. Electromagnetic Capability 

 

 

 

 

 

 

3.1 RF-Electromagnetic field immunity test according to EN61000-6-2:2005, 

EN61000-6-4:2001 

3.2 Power frequency magnetic field immunity test according to EN61000-6-2:2005, 

EN61000-6-4:2001  

3.3 Electrostatic discharge immunity test according to EN61000-6-2:2005, 

EN61000-6-4:2001 

3.4 Surge immunity test according to EN61000-6-2:2005, EN61000-6-4:2001 
3.5 Electrical fast transient/burst immunity test according to EN61000-6-2:2005, 

EN61000-6-4:2001 

Mianyang Weibo Electronic Co.,Ltd 

No.7 Road 2 of Xianren Road Youxian District Mianyang City P.R. China     

Tel: 86-816-2971265 Fax: 86-816-2281934 

www.wb-my.com

2

     

[email protected]

 

 

Summary of Contents for WBV332S01

Page 1: ...nsducer www wb my com wblch wbdz cn Technical Service 86 816 2278271 Quality Complain 86 816 2278273 Fax Line 86 816 2281934 ISO9001 ISO14000 GB T2800 CE Certified Quality Warranty Any quality problem found in WB series products we offer Three years free charge of repair the products and six months guaranteed free charge of change and return the products ...

Page 2: ...ceivable circumstances or include detailed information on all topics In the event of questions or specific problem do not take any action without proper authorization Contact the appropriate WB technical sales office and request the necessary information Standard application 1 Accuracy Accurate degree is conformed to IEC688 1992 2 Safety 2 1 Overload capability Overload capability is conformed to ...

Page 3: ...pure or pulsating voltage into a load independent output signal DC voltage 0 5V or 0 10V It has adopted modulation demodulation isolation principle and average measurement method for real time measurement of DC voltage from electric net The product has certain advantages of total galvanic isolation between input output high accuracy low drifting by temperature and wide temperature bearable range e...

Page 4: ...1MΩ 5 Linear Range 0 120 of nominal input 6 Responding Time 150ms 7 Over Load Capacity 2 times of nominal input continuous 8 Output current 5mA 9 Auxiliary Power 12Vdc 24Vdc 10 Current consumption for static status 10mA 11 Isolation Voltage 2500Vdc for 1 minute 12 Output Ripple 10mV 13 Drifting by Temperature 0 50 100 10 6 14 Ambient Temperature 10 50 15 Mounting DIN Rail 35mm Mounting or screw mo...

Page 5: ... auxiliary power requires isolation voltage 2000VAC DC current output ripple 10mV and multiple converters can share with one set auxiliary power together b When measuring dc voltage exceeds 500 volts the circuit needs adding a resistor to divide the input dc voltage The resistor is provided by Mianyang weibo Electronic and only for each type of transducers special use only 4 Transducer VX 6 Resist...

Page 6: ...transducer it shows the transducer s accurate grade is qualified Caution 1 Pay attention to the auxiliary power information especially the auxiliary power grade and polarity other wise will damage the product 2 Pay attention to the wire connection wrong terminal connection will cause malfunction of the product and even damage the product 3 Don t dismantle the product and carry with care to avoidin...

Page 7: ...s fire prevent ABS crust its temperature withstand is only limited as 85 higher than this limitation will cause the product deformation Please use and store carefully 8 This product can t be used to measure the pulse DC voltage signal otherwise there will be more errors or no output Mianyang Weibo Electronic Co Ltd No 7 Road 2 of Xianren Road Youxian District Mianyang City P R China Tel 86 816 297...