(3) Warming up the transducer for 3 minutes

(4) Use V1 and V3 for monitoring, set one set of

any input value which is within

the measuring range of the transducer Ur (line voltage), Ir, COSφ, (for e.g. if

input value is 100V and 5A, the output is 4-20mA, the expected output value Iz

should be calculated as:

Iz =

20mA

4mA)×│(Ur×Ir×COSφ)/(100V×5A)│

4mA

(5) Using output monitoring meter V2 to measuring the output voltage V0 of the

transducer, the basic introduced error

γ

of the transducer should be calculated

as:

γ= (Vo-Iz×250Ω)/[(20mA-4mA)×250Ω]×100

Repeating step (4) (5), if calculated absolute value is less than the given accuracy value of the

transducer, it shows the transducer’s accurate grade is qualified.

Caution:

Caution:

Caution:

Caution:

1.

Pay attention to the auxiliary power information, especially the auxiliary power grade,

and polarity, other wise will damage the product.

2.

Pay attention to the wire connection; wrong terminal connection will cause

malfunction of the product and even damage the product;

3.

Don’t dismantle the product, and carry with care to avoiding bump and fall of the

product;

4.

If the product has been using under the environment with strong magnetic field

interference, please pay attention to the shield of input wire, and the output signal wire

should be as short as possible. For product intensive installation, the space between

each product should not be smaller than 10mm.

5.

Only use identified terminals.

6.

There is no lightening strike prevention circuit design in this product. For out door and

hazardous environment using, please add protective alternatives.

7.

This product uses fire prevent ABS crust, its temperature withstand is only limited as

+85

, higher than this limitation will cause the product deformation. Please use and

store carefully.

Warranty:

Warranty:

Warranty:

Warranty:

(a) Product Warranty: Seller warrants that upon Delivery the Product to be supplied by

Weibo shall be completely new and shall comply in all respects with the Technical

Summary of Contents for WBP114S41

Page 1: ...er power transducer transducer transducer transducer Single Single Single Single phase phase phase phase www wb my com wbdz yahoo cn Technical Service 86 816 2778271 Quality Complain 86 816 2278273 Fax Line 86 816 2281934 ISO9001 ISO14000 ISO18000 Certified Quality Warranty Any quality problem found in WB series products we offer Three years free charge of repair the products and six months guaran...

Page 2: ...erating manual for the equipment gives instructions for its installation commissioning and operation However the manual cannot cover all conceivable circumstances or include detailed information on all topics In the event of questions or specific problem do not take any action without proper authorization Contact the appropriate WB technical sales office and request the necessary information Stand...

Page 3: ...rifting by temperature and low power consuming etc F F F Function unction unction unction realization realization realization realization schematic schematic schematic schematic drawing drawing drawing drawing Product Product Product Product Dimensional Dimensional Dimensional Dimensional Drawing Drawing Drawing Drawing unit unit unit unit mm mm mm mm Input terminal DIN Mounting Rail Output termin...

Page 4: ... Hz 2 Output 4mA 20mA 3 Accuracy 0 5 4 Input Impedance R When UX 10V RU UX 1KΩ V 5 Linear Range V 10 120 of nominal input I 1 120 of nominal input COSφ 0 1 lag 1 0 1 lead 6 Responding Time 300 ms 7 Over Load Capacity 2 times of nominal input voltage continuous 20 times of nominal input current continuous 8 Maximum Load 6V 9 Auxiliary Power 12 Vdc 24Vdc 10 Current consumption for static status 25mA...

Page 5: ...tly wiring it can be powered and used immediately But for further precise signal sampling user needs to warm up the product for 3 minutes before use a The auxiliary power requires isolation voltage 2000VAC DC current output ripple 10mV and multiple converters can share with one set auxiliary power together b Output signal Iz is designed to follow the impedance load value of 250Ω When Resistance R1...

Page 6: ...ary power grade and polarity other wise will damage the product 2 Pay attention to the wire connection wrong terminal connection will cause malfunction of the product and even damage the product 3 Don t dismantle the product and carry with care to avoiding bump and fall of the product 4 If the product has been using under the environment with strong magnetic field interference please pay attention...

Page 7: ...duct and any purchase made in six months Weibo will provide free charge of change and return the product if damage and problem caused by product quality Note Transportation fee of repaired and returned product will be borne by Buyer Product Product Product Product Input Output Input Output Input Output Input Output characteristic characteristic characteristic characteristic curve curve curve curve...

Reviews: