Step 1: Immobilize one side of product‘s mounting trough to
the DIN mounting rail;
Step 2: Pull out the spring clasp;
Step 3: Place whole mounting trough to the DIN mounting rail
properly;
Step 4: Release spring clasp to make sure the installation.
2.
The product has calibrated before out of factory. After correctly
wiring, it can be powered and used immediately. But for further
precise signal sampling, user need to warm-up the product for 3
minutes before use. The auxiliary power requires isolation
voltage≥2000V AC, DC current output ripple
<
10mV.
3.
Basic testing method for accuracy
(1)
According to the terminal definition table to connect the
testing circuit;
(2)
The testing must to be done by under the following
conditions
;
Power supply: nominal value
±
0.5
%
, ripple
≤
5mV
Ambient temperature: 25
℃±
5
℃
Relative humidity: RH(45
~
75)
%
Accuracy for Signal Power Source instrument: 0.05
(3)
Warming up the transducer for 3 minutes
(4)
Use the input monitoring table V1 to monitor the output of
Sig
nal
T
ransducer
Power supply
V
1
J
K
1
5
3
1
3
1
JK2
+
+
-
-
R
R
V
2
GND
+E