background image

13

14

P ASS  CODE

00

O/ V  SETTI NG_

O/ V  TRI P %  REL AY

105

AUTO

O/ V  CL EAR%  DEL AY

103

01. 00

U/ V  SETTI NG_

U/ V  TRI P %  REL AY

095

AUTO

U/ V  CL EAR%  DEL AY

01. 00

097

ADJ USTMENT_

VOL TAGE

380

CHECK

RECORD

RECORD

CHECK

PROG

PROG

PROG

RECORD

RECORD

PROG

PROG

PROG

CHECK

RECORD

RECORD

PROG

PROG

PROG

CHECK

RECORD

RECORD

PROG

PROG

PROG

RECORD

RECORD

PROG

PROG

PROG

CHECK

RECORD

RECORD

PROG

PROG

PROG

U/ V  L O  L I MI T%

000

CHECK

RECORD

RECORD

PROG

PROG

PROG

P T  RATI O

0001

RECORD

RECORD

PROG

PROG

PROG

F REQUENCY

50

RECORD

RECORD

PROG

PROG

PROG

CHECK

RECORD

4.3 Configuration descriptions: 'PROGRAM' LED is ON 

Enter Password: 

Range: 00 - 99

00 = Password disable

Enter into value setting, digit flashing

Value increase, long press to increase speed

Value decrease, long press to increase speed

Confirm setting, enter into Setting if password is right

'ERROR' will show if it is wrong password.

O/V Setting main menu

O/V Trip % and Relay setting

Range: Trip%: 100-130%, Relay: OFF, AUTO, LATCH

Enter into value setting, digit flashing

Move the cursor to next digit

Value increase, long press to increase speed

Value decrease, long press to increase speed

Confirm setting and return to sub menu

Move the cursor to next digit

RELAY: OFF (Non operation), AUTO: Auto reset, LATCH: Manual reset (Press reset button to reset)

O/V Reset % and Delay setting

Range: Reset%: 100-130%, Delay time: 00-60sec

Enter into value setting, digit flashing

Move the cursor to next digit

Value increase, long press to increase speed

Value decrease, long press to increase speed

Confirm setting and return to sub menu

U/V Setting main menu

Range: Trip%: 70-100%, Relay: OFF, AUTO, LATCH

U/V Trip % and Relay setting

Enter into value setting, digit flashing

Move the cursor to next digit

Value increase, long press to increase speed

Value decrease, long press to increase speed

Confirm setting and return to sub menu

RELAY: OFF (Non operation), AUTO: Auto reset, LATCH: Manual reset (Press reset button to reset)

U/V Reset % and Delay setting

Range: Reset%: 70-100%, Delay time: 00-60sec

Enter into value setting, digit flashing

Move the cursor to next digit

Value increase, long press to increase speed

Value decrease, long press to increase speed

Confirm setting and return to sub menu

U/V Low limit % setting

Range: 000-100%

Enter into value setting, digit flashing

Move the cursor to next digit

Value increase, long press to increase speed

Value decrease, long press to increase speed

Confirm setting and return to sub menu

Adjustment setting main menu

PT ratio setting

Range: 60-480V

System Voltage setting

Enter into value setting, digit flashing

Value increase, long press to increase speed

Value decrease, long press to increase speed

Confirm setting and return to sub menu

Range: 0.001-9999, Press            to change decimal place

Enter into value setting, digit flashing

Value increase, long press to increase speed

Value decrease, long press to increase speed

Confirm setting and return to sub menu

Frequency setting
Range: 50 or 60Hz

Enter into value setting, digit flashing

Value increase, long press to increase speed

Value decrease, long press to increase speed

Confirm setting and return to sub menu

Summary of Contents for OUV-400

Page 1: ...Mun hean singapore Pte Ltd RELAY STATUS PROG CHECK FUNCTION PROGRAM CHECK RECORD TRIP RECORD RESET TEST OPERATION MANUAL OUV400 OVER VOLTAGE UNDER VOLTAGE 01 2021 L12 380 V L23 380 V OVER UNDER VOLTAG...

Page 2: ...Indicators Program Programming mode Check Display of setting Record Display of memory records Type of Fault indicator Over Voltage Under Voltage Trip status indicator Function buttons Test and Reset...

Page 3: ...3 2 Long press to return to the numeric display screen Enter the setting main menu refer to 4 1 Trip test function keys Normal Non trip condition Press once to show PRESS TEST AGAIN TO CONFIRM Press...

Page 4: ...t U V CLEAR DELAY 97 0 100 OV Reset level setting Delay time sec U V LO LIMIT 000 UV non operating zone setting RTC YYYY MM DD 09 06 2020 RTC Real Time Clock setting Available for model wtih RTC RTC R...

Page 5: ...oltage setting Over Voltage threshold setting at 105 Over Voltage contact operation setting AUTO Auto reset CHECK mode ON indication O V CLEAR DELAY O V Over Voltage setting Over Voltage Reset value s...

Page 6: ...Trip memory record display Refer to 3 4 Latest trip record memory Record LED indicates it is in Record memory page Present status Trip LED indicates the relay had trip Overvoltage LED indicates Overv...

Page 7: ...E RELAY OVER UNDER VOLTAGE RELAY OVER UNDER VOLTAGE RELAY OVER UNDER VOLTAGE RELAY Over Voltage Under Voltage OUV400 Over Voltage Under Voltage OUV400 Over Voltage Under Voltage OUV400 Over Voltage Un...

Page 8: ...ncrease speed Value decrease long press to increase speed Confirm setting and return to sub menu U V Setting main menu Range Trip 70 100 Relay OFF AUTO LATCH U V Trip and Relay setting Enter into valu...

Page 9: ...sub menu Enter into value setting digit flashing Value increase long press to increase speed Value decrease long press to increase speed Confirm setting and return to sub menu Over thershold Flashing...

Page 10: ...f full scale Time accuracy 3 of trip time or 20ms Whichever is greater 10 Tripping Relay overvoltage Contact 1c 250Vac 5A undervoltage Contact 1a 250Vac 5A 11 LCD indication 16 x 2 display Real time 3...

Page 11: ...Start Address Lo Number of Word Lo Number of Word Hi Error Check End of Frame 01H FFH 03H 0 nnH 1 nnH CRC Lo CRC Hi 0 nnH 0H 1 Byte 2 Bytes 1 Byte 2 Bytes 2 Bytes Response no error received Start of F...

Page 12: ...x22 0xe2 0xe3 0x23 0xe1 0x21 0x20 0xe0 0xa0 0x60 0x61 0xa1 0x63 0xa3 0xa2 0x62 0x66 0xa6 0xa7 0x67 0xa5 0x65 0x64 0xa4 0x6c 0xac 0xad 0x6d 0xaf 0x6f 0x6e 0xae 0xaa 0x6a 0x6b 0xab 0x69 0xa9 0xa8 0x68 0...

Page 13: ...12 1 31 0 23 0 59 0 59 0 100 1 12 1 31 0 23 0 59 0 59 6 8 Data register Integer format Setting parameter Address Hex Contents Format Word Access Range Unit 0000 0001 0002 0003 0004 0005 0006 0007 000...

Page 14: ...2 L2 L3 4 L3 L1 Multiple phase tripping is possible If reading is 3 2 1 it will indicate that L1 L2 and L2 L3 are having fault 0 Nil 1 L1 L2 2 L2 L3 4 L3 L1 8 Test 0 Nil 1 L1 L2 UV 2 L2 L3 UV 4 L3 L1...

Reviews: