1.5.2
Output
Power factor:
0.9 lagging
Total harmonic distortion
< 2% (linear load)
(THD):
< 4% (for 100% non-linear load with a crest factor of up to 3.5)
Transient regulation:
± 1% for balanced load ± tbd for 100% unbalanced load
Transient response:
± tbd for 100% step load change
Overload:
125% of rated load for 10 minutes (750-800 kVA), 10 minutes (555-625 kVA),
150% of rated load for 1 minute
1.5.3
Mechanical
Height:
82 in/2083 mm
Depth:
39 in/991 mm
Width:
See Table 2-1
Weight:
See Table 2-1
Finish:
MGE light gray
1.5.4
Environmental
Recommended environment:
20° to 25° C (68° to 77° F); 50% relative humidity; computer room or other temperature-
and humidity-controlled environment
Operating temperature:
0° to 40° C (32° to 86° F) except battery
Storage:
-20° to 50° C (-4° to 122° F)
Humidity:
up to 90% non-condensing (operating)
Altitude:
sea level to 1,000 meters (sea level to 3,280 feet) without derating; 1,000 to 2,000
meters (3,280 to 6,560 feet): derate operating temperature to a maximum of 28° C
(82° F)
Introduction
EPS 7000 Single and Shared Systems
page 1 — 6
Summary of Contents for EPS 7000
Page 1: ...EPS 7000 Single Module and Shared Systems Installation Manual w w w m g e u p s c o m...
Page 10: ...This page left blank intentionally EPS 7000 Single and Shared Systems page c iv...
Page 36: ...This page left blank intentionally EPS 7000 Single and Shared Systems page 3 8 Installation...
Page 44: ...This page left blank intentionally EPS 7000 Single and Shared Systems page g 6...
Page 46: ......
Page 47: ......
Page 48: ...1660 Scenic Avenue Costa Mesa California 92626 714 557 1636 w w w m g e u p s c o m...