For backfeed protection, an upstream protective device, marked Q4S on the installation
drawings, must be supplied by the customer. Q4S, which will supply the SSC, must be
equipped with a 24 VDC shunt trip and a normally open auxiliary switch.
The steps to be followed are:
•
Identification of all installation drawings.
•
Placement of the static switch cabinet (SSC), UPS modules, and
applicable battery and auxiliary cabinet(s).
•
Connection of input power, output power, and inter-cabinet control
and power cables.
•
Start-up of the system.
Installation of UPS equipment must be handled by skilled technicians and electricians familiar
with the special requirements of high-energy electrical equipment. The installation must comply
with the requirements of the National Electrical Code (NEC, ANSI/NFPA 70, latest issue) and
with local codes and requirements as applicable.
Move the EPS 6000 UPS module, battery cabinet(s) (if
any), and auxiliary cabinet(s) (if any), to their final location,
as described in the Mechanical considerations section. For cabinets installed adjacent to each
other, alignment is critical to properly install the spacers and cabinet interconnects. Refer to
the installation drawings for handling, removing the cabinet from the pallet, placement,
alignment, and mechanical connections.
Remove the packing materials and lift the enclosures to remove the pallets. Refer to
the handling instructions and installation drawings supplied with the equipment for
pallet removal procedures.
3.5.1
Placement
3.5
Installation
Procedure
S o m e a d j a c e n t c a b i n e t s a r e j o i n e d m e c h a n i c a l l y
u s i n g c o p p e r s t r a p s , w h i c h a l s o p r o v i d e t h e
e l e c t r i c a l g r o u n d p a t h b e t w e e n c a b i n e t s . P r o p e r
a l i g n m e n t o f a d j a c e n t c a b i n e t s a n d p r o p e r
i n s t a l l a t i o n o f t h e s e s t r a p s i n c o m p l i a n c e w i t h t h e
i n s t a l l a t i o n d r a w i n g s i s c r i t i c a l t o a s a f e
i n s t a l l a t i o n .
WARNING
3 — 3
Installation, Shared Systems
Installation manual
Summary of Contents for EPS 6000
Page 1: ...EPS 6000 UPS Uninterruptible Power Systems Installation Manual...
Page 10: ...this page left blank intentionally EPS 6000 Uninterruptible Power System...
Page 40: ...this page left blank intentionally EPS 6000 Uninterruptible Power System...
Page 50: ...this page left blank intentionally EPS 6000 Uninterruptible Power System...
Page 70: ......
Page 71: ......