This section describes installation of the single EPS 6000
UPS, including receiving, handling, and storage procedures;
prerequisites to the installation; installation procedures; and start-up procedures.
Before accepting the shipment from the freight carrier,
inspect the exterior surfaces of all shipping containers or
packaging used, and the equipment, for damage that may have occurred during transit. If the
shipping containers or equipment show evidence of damage, note the damage on the
receiving document (bill of lading) prior to signing for receipt of equipment.
The equipment should be unpacked immediately after receipt, and inspected again to
determine if any internal shipping damage (broken components, disconnected wiring, loose
connections, etc.) has occurred. Verify that the equipment nameplate(s) correspond with the
equipment ordered.
Damage claims should be filed directly with the carrier. Replacements for damaged
components should be ordered through MGE Customer Support Services at 1-800-438-7373.
Carefully follow the handling instructions attached to the
shipping materials. EPS 6000 enclosures are shipped on a
shipping pallet for protection. Do not move the enclosures more than a few feet without their
pallets. Generally, EPS 6000 cabinets can be forklifted, roll-a-lifted, slinged; carefully follow the
handling instructions for restrictions/precautions.
If the equipment is to be stored prior to installation, it should
be stored in a cool, dry, well-ventilated location that is
protected against rain, splashing water, chemical agents, etc. The equipment should be
covered with a tarpaulin or plastic wrapper to protect it against dust, dirt, paint, or other
foreign materials.
B a t t e r i e s s h o u l d b e s t o r e d n o l o n g e r t h a n t h r e e ( 3 )
m o n t h s a t 2 5
°
C ( 7 7
°
F. ) o r l o w e r p r i o r t o
r e c h a r g i n g . E x c e e d i n g t h e r e c o m m e n d e d a m b i e n t
s t o r a g e t e m p e r a t u r e w i l l r e d u c e b a t t e r y b a c k - u p
t i m e a n d m ay a dv e rs e ly a f fe c t b a t t e r y l i fe .
IMPORTANT
2.3
Storage
2.2
Handling
2.1
Receiving
2.0
Scope
2 — 1
Installation, Single-Module Systems
Summary of Contents for EPS 6000
Page 1: ...EPS 6000 UPS Uninterruptible Power Systems Installation Manual...
Page 10: ...this page left blank intentionally EPS 6000 Uninterruptible Power System...
Page 40: ...this page left blank intentionally EPS 6000 Uninterruptible Power System...
Page 50: ...this page left blank intentionally EPS 6000 Uninterruptible Power System...
Page 70: ......
Page 71: ......