mFi Mason-Lite MFPST43 Instructions Manual Download Page 17

16

Fireplace Finishes & Combustible Trim 

Clearances

Hearth Material & Dimensions – Codes are strict regarding the 

use of proper materials for hearth extensions and the proper 

dimensional characteristics.
 All hearth extensions must be made of code-rated, 

noncombustible materials such as tile, brick, concrete or 

stone. MASON-LITE Fireplaces usually have an opening of 

approximately 8 sq. ft. (eight square feet) that translates to a 

hearth extension of about 20” (twenty inches) at the fireplace’s 

opening and about 12” (twelve inches) extension at each side. 

These relative dimensions are also covered by code.    

Figure 35

43"

NON-COMBUSTIBLE 

HEARTH EXTENSION 

BOTH SIDES

1

1
2

"

24" min

12

20

30"

20"

GRATE SIZED

50% OF HEARTH 

AREA MAX.

 

Note that it is required that metal safety strips must be laid on 

the floor of the non-combustible raised platform. These should 

be 26 gauge and measure 4” (four inches) wide. They need 

to extend half way under the platform and half way under the 

hearth extension material (see Figure 19). 

Attention:

 You will note that there will be a gap between the 

fireplace front and the extension of the non-combustible hearth 

material. Be certain that you seal this with non-combustible 

material.       

1/2" THICK 

CONCRETE

BOARD

CLASS "A" 

CHIMNEY

SEE FIG. 

29 AND 30

SEE FIG. 27

2" AIRSPACE 

CLEARANCE TO 

COMBUSTIBLES

ON REAR AND 

SIDES OF UNIT.

ONLY NON-COMBUSTIBLE 

MATERIAL WITHIN 18” OF 

TOP OF OPENING.

28”

8” METAL

PLATFORM

1/2”

2”

seal gap with 

non-combustible 

material

Figure 36

Mantle and Mantle Shelf Clearances 

As with any radiant heat fireplace, all MASON-LITE Fireplaces 

must comply with building code safety clearances, for units 

that have openings of 6 sq. ft. (six square feet) or greater.
For Mantel clearances see Figure 9. 

Walls that Adjoin – your fireplace cannot be installed closer 

than 2 ft. (two feet) to any adjoining walls in the room where  

the fireplace is.

Caution in Regards to Combustibles – If any part of the 

fireplace or objects in the room (curtains, rugs, paint, cushions, 

etc.) start to show warping or discoloration due to heat from 

the fireplace, it is time to take immediate action. Do not use 

the  fireplace  until  you  have  figured  out  how  to  address  the 

problem. You are facing a potential fire hazard. MFI cannot be 

responsible for the make-up of material on the exterior of the 

fireplace you have chosen, nor can MFI be held responsible 

for the materials in a room that may be responding negatively 

to heat. However, in almost all cases, there is a solution to 

the problem, either by making adjustments to airflow or the 

modifications to the room itself.

Installing Outside Combustion (make-up) Air

1) The Mason-Lite Fireplace needs enough make-up air to 

function properly and some local building codes may require 

outside combustion air to be provided. If no make-up air is 

provided, improper flue drafting may occur, creating negative 

pressure whereby smoke may enter the home, especially in 

homes that are very well insulated and tightly sealed. Check 

local building codes for specific requirements.

2) Install Combustion Air Kit MFP4-AK into the MASON-LITE 

Firebox through the side wall opening provided. The tubing 

that goes out of the firebox wall must feed into a flexible metal 

conduit as the source for outside combustible air. It can go 

straight out through an outside wall or into a ventilated crawl 

space. If crawl space is used, check codes for proper 

termination. 

      

Figure 37

Internal

Wall

Installation

Island

Installation

Outside Air supply 

from side wall or 

ventilated crawlspace

Outside Air supply 

from crawlspace

Summary of Contents for Mason-Lite MFPST43

Page 1: ...is book is valuable In addition to instructing you on how to install and maintain your appliance it also contains information that will enable you to obtain replacement parts or accessory items when n...

Page 2: ...STIBLE SHEATHING ABOVE OPENING TOP 18 457 mm SHEATHING OR TRIM TO OPENING SIDES 8 203 mm MANTLE ABOVE OPENING 12 305 mm OPENING TO SIDE WALL 24 610 mm HEARTH EXTENSION BEYOND FRONT 20 508 mm HEARTH EX...

Page 3: ...rts Diagrams MFPST43 Fireplace Parts Diagrams Combustible Floor System Parts Combustible Floor System Parts Fireplace Parts Diagram Fireplace Parts Diagram 10 11 9 5 6 4 7 8 12 2 1 14 3 13 17 18 19 Fi...

Page 4: ...LL WITH OUTSIDE AIR KIT ACCESS 4 HOLE 1 3 SIDE WALL 7 4 LOWER SIDE DOME 2 5 LINTEL 2 6 LOWER DOME FRONT 2 7 53 X4 X 3 X 1 4 ANGLE IRON 2 8 SPILL SWITCH BAFFLE 2 9 UPPER SIDE DOME 2 10 UPPER DOME FRONT...

Page 5: ...8 57 I D FRAMING 18 MIN 2 MIN 2 MIN 2 MIN 2 MIN Non Combustible Floor Systems Figure 4 IF WOOD FRAMING IS UTILIZED IT MUST BE HELD 18 INCHES MIN FROM TOP OF LINTEL AND 2 INCHES MIN CLEARANCE MUST BE M...

Page 6: ...te note that a combustible wood header must be no closer than 2 to the top of the dome top Figure 5 Combustible Floor 28 57 I D FRAMING 2 MIN 2 MIN 20 MIN 2 MIN 12 MIN Not provided as part of fireplac...

Page 7: ...nce manufacturer s literature regarding sizing and suitability for the installation into this Enclosure prior to installation Statement of Intended Use The Mason Lite Masonry Fireplace is a modular re...

Page 8: ...ements Choice of materials and craftsmanship in fireplace and hearth finishing Note that each of these topics will be covered in detail and that the installer is expected to understand each phase comp...

Page 9: ...himney System 2 This Mason Lite fireplace is intended as a supplemental heat source only It is not intended as a primary heat source 3 It is the responsibility of the contractor installer not the manu...

Page 10: ...he floor joists Note that additional floor joists may be required to support the weight of the firebox and chimney Where the floor joists run parallel to the front of the firebox anchorage can be acco...

Page 11: ...bers having a moisture content of less than 16 per cent at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be substituted for the deflection res...

Page 12: ...ce are made of Mason Lite s incredibly strong blend of specialty cement and a light weight aggregate IMPORTANT When applying mortar it is imperative that the concrete blocks be maintained moist not so...

Page 13: ...y threading mortar as you stack each section one onto the next Constantly check for squareness and levelness while building each MFPST43 Fireplace Assembly MFPST43 Fireplace Assembly Field Assembly Pr...

Page 14: ...s have such holding power you should look over the firebox assembly at the end and fill in any gaps especially joint connections with the mortar Needless to say you must make adjustments to be sure th...

Page 15: ...tallations at each floor penetration above that where the Support Box is located as shown in Figure 29 Figure 29 Firestop Spacer with Living Space Above Ceiling Firestop Spacer Existing C e i l i n g...

Page 16: ...shed Height to Combustible Floor Disclaimer Masonry Fireplace Industries wishes to express that as the manufacturer of Mason Lite Fireplaces they cannot take any liability or responsibility for they w...

Page 17: ...r greater For Mantel clearances see Figure 9 Walls that Adjoin your fireplace cannot be installed closer than 2 ft two feet to any adjoining walls in the room where the fireplace is Caution in Regards...

Page 18: ...consequences resulting in an accident or malfunction If instructions are not followed the warranty on the product will become null and void Note that the most important aspect of the installation is...

Page 19: ...ed all elements of the fireplace and chimney system must be completely dry This means that the unit must stand without any firing for a minimum of 28 days Only after that period of time can a first li...

Page 20: ...exible brush from the top of the section downward to the elbow Then clean from the firebox up to the offset return section Be sure that you have covered the floor of the fireplace and out to the heart...

Page 21: ...slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MINIMUM...

Page 22: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Page 23: ...his warranty makes MFI or any affiliate thereof liable in any respect for any injury or damage to the building or structure in which the fireplace has been installed or to the persons or property ther...

Reviews: