mFi Mason-Lite MFPST43 Instructions Manual Download Page 13

12

1)  Place the Mason-Lite Fireplace hearth base on top of your 

non-combustible floor or metal base. For concrete slabs, 

supporting floor needs to be rated at ASTM 90. 

2)  a) 

Combustible Floor Installations: 

 

Mix up a batch of mortar and place hearth slabs on  

  top of cement board which sits on top of the Raised  

  Metal Platform (see Figure 18). All-thread rods should  

  stick up through the holes on the hearth slabs. 

 

HEARTH PIECE

ALL-THREAD 12”

WASHER/NUT

CONCRETE BOARD 

(NOT PROVIDED)

METAL

BASE

INSULATION 

BLANKET

WASHER/NUT

WASHER/NUT

ALL-THREAD 6”

PLYWOOD SHEATHING

EMBER SHIELD 

(UNDER FP OPENING)

FLOOR JOIST 

BRACKET

Figure 18

 

b) 

Non-combustible Floor Installations: 

 

Draw an outline of the hearth area based on the 

  dimensions shown in Figure 19. Position Hearth slabs 

  and mark rebar center locations. 

Figure 19

Four 26ga.galv. 4” wide

Hearth Ember Shields 

required (not supplied)

LH Hearth 2nd

RH Hearth 1st

53”

28”

Apply mortar 

between joints

2” min 

overlap typ.

 

  Drill 4 inches into concrete slab and secure the four 

  pieces of rebar with epoxy (Figure 20).   

 

 

Drill Ø5/8” hole 

x 4” deep

Epoxy #3 rebar 

centered into hole.

Use ITW Epoxy or 

Simpson Epoxy.

For concrete 

foundations 

less than 6” 

thick, drill 

slanted.

Figure 20

3) 

Before installing the side walls, confirm placement of 

outside combustion air side block (if required), this can 

be installed either side depending on which side is 

accessible to outside combustion air. Prepare side wall 

footprint with the prepared mortar.

4) 

Keep the assembly of the next sections of the firebox 

side walls moving up, keeping components moist, mixing 

mortar as you need it and properly threading mortar as 

you stack each section, one onto the next. Constantly 

check for squareness and levelness while building each 

MFPST43 Fireplace Assembly

MFPST43 Fireplace Assembly

 

 Field Assembly Procedures

Field Assembly Procedures

a)  Mixing the MASON-LITE mortar – The mortar comes 

premixed and should be dry. Be sure to use clean water and 

work it up into a mixture that is pasty but not lumpy. If it’s 

too thin and the surfaces don’t stay moist, the components 

will not adhere. Load the mixture into a standard grout bag.

b)  Apply about ½” (one-half inch) thread of mortar. The mortar 

bead should be approximately ½” (one-half inch) away from 

all edges. The mortar has a considerable amount of holding 

power so do not overload the components with too much 

mortar. Keep the components moist at all times!

c)  Some mortar will “ooze out” when placing components 

together, this is normal. Wipe excess away with a trowel. Do 

not cover component surfaces completely with mortar. Do 

not apply the mortar in thick bands even if the component 

you are working with is larger than the rest. You will want to 

apply “stripes” of mortar in these situations.

d)  Make sure components are level. It’s extremely important 

that you pay careful attention to how you are assembling 

the Mason-Lite Fireplace since every component builds on 

the next. If you have to make any kind of an adjustment, 

do not try to do it “by loading an opening” with mortar, this 

will only result  in a fireplace that will not be plumb or level.

 

Use wood shims instead. 

You will find these small wood 

shims supplied with the Mason-Lite Fireplace

 and 

you can nudge them in between openings to achieve the 

precision you need in making component adjustments. 

Once you have inserted any shims, you will want to 

cover any gaps that may have resulted with the mortar. 

Summary of Contents for Mason-Lite MFPST43

Page 1: ...is book is valuable In addition to instructing you on how to install and maintain your appliance it also contains information that will enable you to obtain replacement parts or accessory items when n...

Page 2: ...STIBLE SHEATHING ABOVE OPENING TOP 18 457 mm SHEATHING OR TRIM TO OPENING SIDES 8 203 mm MANTLE ABOVE OPENING 12 305 mm OPENING TO SIDE WALL 24 610 mm HEARTH EXTENSION BEYOND FRONT 20 508 mm HEARTH EX...

Page 3: ...rts Diagrams MFPST43 Fireplace Parts Diagrams Combustible Floor System Parts Combustible Floor System Parts Fireplace Parts Diagram Fireplace Parts Diagram 10 11 9 5 6 4 7 8 12 2 1 14 3 13 17 18 19 Fi...

Page 4: ...LL WITH OUTSIDE AIR KIT ACCESS 4 HOLE 1 3 SIDE WALL 7 4 LOWER SIDE DOME 2 5 LINTEL 2 6 LOWER DOME FRONT 2 7 53 X4 X 3 X 1 4 ANGLE IRON 2 8 SPILL SWITCH BAFFLE 2 9 UPPER SIDE DOME 2 10 UPPER DOME FRONT...

Page 5: ...8 57 I D FRAMING 18 MIN 2 MIN 2 MIN 2 MIN 2 MIN Non Combustible Floor Systems Figure 4 IF WOOD FRAMING IS UTILIZED IT MUST BE HELD 18 INCHES MIN FROM TOP OF LINTEL AND 2 INCHES MIN CLEARANCE MUST BE M...

Page 6: ...te note that a combustible wood header must be no closer than 2 to the top of the dome top Figure 5 Combustible Floor 28 57 I D FRAMING 2 MIN 2 MIN 20 MIN 2 MIN 12 MIN Not provided as part of fireplac...

Page 7: ...nce manufacturer s literature regarding sizing and suitability for the installation into this Enclosure prior to installation Statement of Intended Use The Mason Lite Masonry Fireplace is a modular re...

Page 8: ...ements Choice of materials and craftsmanship in fireplace and hearth finishing Note that each of these topics will be covered in detail and that the installer is expected to understand each phase comp...

Page 9: ...himney System 2 This Mason Lite fireplace is intended as a supplemental heat source only It is not intended as a primary heat source 3 It is the responsibility of the contractor installer not the manu...

Page 10: ...he floor joists Note that additional floor joists may be required to support the weight of the firebox and chimney Where the floor joists run parallel to the front of the firebox anchorage can be acco...

Page 11: ...bers having a moisture content of less than 16 per cent at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be substituted for the deflection res...

Page 12: ...ce are made of Mason Lite s incredibly strong blend of specialty cement and a light weight aggregate IMPORTANT When applying mortar it is imperative that the concrete blocks be maintained moist not so...

Page 13: ...y threading mortar as you stack each section one onto the next Constantly check for squareness and levelness while building each MFPST43 Fireplace Assembly MFPST43 Fireplace Assembly Field Assembly Pr...

Page 14: ...s have such holding power you should look over the firebox assembly at the end and fill in any gaps especially joint connections with the mortar Needless to say you must make adjustments to be sure th...

Page 15: ...tallations at each floor penetration above that where the Support Box is located as shown in Figure 29 Figure 29 Firestop Spacer with Living Space Above Ceiling Firestop Spacer Existing C e i l i n g...

Page 16: ...shed Height to Combustible Floor Disclaimer Masonry Fireplace Industries wishes to express that as the manufacturer of Mason Lite Fireplaces they cannot take any liability or responsibility for they w...

Page 17: ...r greater For Mantel clearances see Figure 9 Walls that Adjoin your fireplace cannot be installed closer than 2 ft two feet to any adjoining walls in the room where the fireplace is Caution in Regards...

Page 18: ...consequences resulting in an accident or malfunction If instructions are not followed the warranty on the product will become null and void Note that the most important aspect of the installation is...

Page 19: ...ed all elements of the fireplace and chimney system must be completely dry This means that the unit must stand without any firing for a minimum of 28 days Only after that period of time can a first li...

Page 20: ...exible brush from the top of the section downward to the elbow Then clean from the firebox up to the offset return section Be sure that you have covered the floor of the fireplace and out to the heart...

Page 21: ...slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MINIMUM...

Page 22: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Page 23: ...his warranty makes MFI or any affiliate thereof liable in any respect for any injury or damage to the building or structure in which the fireplace has been installed or to the persons or property ther...

Reviews: