16
7 ND91P 70 en
❑
After the desired value is displayed, press the
key
?
to conclude the operation.
5.5.6 Valve rotation direction,
ROT
The application-specific parameter
ROT
defines the rela-
tionship between position sensor rotation and valve action.
❑
Once
ROT
is displayed press the
?
key to enter
the edit state and
ROT
starts to blink.
❑
Now you may select between two values by
pressing the
+
or
-
key. The value
cC
indicates
clockwise rotation for closing the valve and
ccC
means counterclockwise to close.
❑
After the desired value is displayed, press the
key
?
to conclude the operation.
5.5.7 Valve dead angle,
A0
The
α
0
setting is made for Metso segment and ball valves.
This setting takes into account the "dead angle"
α
0
of the
ball valves. The entire signal range is then used for effec-
tive valve opening 90° -
α
0
. Use 0 % as the "dead angle"
for the valves not mentioned in Table 5.
❑
After selecting
A0
on the display, press the
?
key to enter the edit state and
A0
starts to blink.
The value currently selected appears as a per-
centage (
%
) on the display.
❑
Modify the parameter value by pressing
+
or
-
keys alternately until the desired value appears
on the display.
❑
Press the
?
key to make your selection and
return to the setting state.
5.5.8 Profibus slave address setting
❑
You can modify the Profibus slave address by
pressing
+
and
-
keys. Range is 0-126, default
value is 126.
❑
Press the
?
key to make your selection and
return to the setting state.
5.5.9 Language selection,
LANG
❑
Select between three languages
EnG
,
GEr
or
FrE
using the
+
and
-
keys.
❑
To conclude press the
?
key when the desired
value is shown on the display.
5.5.10Low limit, high cutoff, high limit
ND9100P supports signal cutoff and limiting in both
ends of the operating range. The configuration parame-
ters are; low cutoff, low limit, high cutoff and high limit.
❑
If the input signal is smaller than low cutoff,
the valve will be fully closed.
❑
If the input signal is smaller than low limit,
the valve stays in the low limit.
❑
If the input signal is greater than high cutoff,
the valve will be fully opened.
NOTE:
Perform valve calibration and tuning always when con-
troller fail action parameter has been changed.
NOTE:
Perform valve calibration and tuning always when
ROT
has been changed.
Taulukko 5 Dead angle in percentage
Valve
size
Valve series
MBV
QMBV
1)
MBV
QMBV
2)
D,
P,
C
T5,
QT5
QX-
T5
T25,
QT25
QX-
T25
R,
QR
E
R-
SOFT
3)
FL
4)
ZX
mm
in
Dead angle, %
15
1/2
15
20
3/4
15
25
1
14
-
-
25.5 19.5
-
-
15
25.5
27
12.5
25/1 1/1
14.5
11
25/2 1/2
8
11
25/3 1/3
8
10
25/4
8
40 1 1/2 12
-
-
24.5 12.5
-
-
12
16
21
12.5
50
2
10
9
13.5 24.5 12.5
18
8
17
20.5
23
12.5
65 2 1/2
9
-
-
-
-
-
-
13
-
18
80
3
10
8
12
18
8
16.5 8.5
9
8.5 15.5
100
4
10
8
12
16.5 8.5
16
9
8
7
14.5
125
5
12
-
-
-
-
12
6.5
8
-
150
6
10
8
11.5
16
9
13.5
8
13.5
13
200
8
9
7
8.5
12
6.5
9.5
7
11.5
250
10
9
7
7.5 13.5
9.5
7
10.5
300
12
8
6
6.5
9.5
7.5
6
9.5
350
14
6
6
-
5
9.5
400
16
5
5.5
9.5
(14")
5
9.5
450
18
6
7.5
(16")
500
20
6
4.5
600
24
5.5
6
650
26
7
700
28
7
6
750
30
6
800
32
-
900
36
5.5
1) Seat supported 2) Trunnion 3) Soft seated R-valve 4) Low Cv Finetrol
Fig. 14
Principle of setting
Fig. 15
Dead angle
100
80
60
40
20
0
0
20
40
60
80
100
α
0
Position
Input signal
low cut-off safety range 2
±
0.5 %
Basic setting
α
0
setting