DPU Bus Troubleshooting
Metso Automation MAX Controls
••••
277581
••••
3-6
zeroed. Status broadcasts are issued only
when a station sees a status change:
•
DBM, WorkStation, 58x Operator Station
•
DPU Bus Cable status change
•
Remote (Diagnostic) alarm status
change
•
Controller File, DPU
•
Cable status change
•
Remote (diagnostic) alarm status
change
•
Process alarm status change
Total q/r transactions
The number of query/response transactions
completed by this station.
Received frames with
errors
The number of massage frames received with
errors.
Unfinished
transmit queries
The number of times this station was unable
to complete its pending transactions in the
time allotted for mastership; a measure of
how busy the DPU Bus and this station are,
but not errors.
CRC
errors
The number of frames received which
contained an error detected by the cyclic
redundancy check (CRC) bytes at the end of
each frame.
Stallout recoveries
The number of times this station attempted to
recover from a stallout.
Overrun errors
The number of times this station's DPU Bus
processor could not process data as fast as it
was coming in from the DPU Bus.
Received frame
length
errors
The number of rejected frames because the
frame length received was incorrect.
Message retries
The number of times this station could not
complete a transaction and retried to complete
it; includes token passes to non-existent
stations.
Unexplained errors
The number of frames received with errors
not categorized above.