METROTEC
27
Data request at protocol Modbus RTU, 8bit, 1 Stopbit, Even
Adress
Function
Storage adress
Registers
CRC 1
CRC 2
03
Byte1 Byte2
Byte1 Byte2 Byte
Byte
Excample for a request at address 1 in HEX-display
Measurement value
% O
2
01
03
80
A4
00
02
AC
2B
log O
2
01
03
80
A6
00
02
0D
E8
ppm O
2
01
03
80
A8
00
02
6C
2B
TP
01
03
80
AA
00
02
CD
EB
O
2
red
01
03
80
AC
00
02
2D
EA
Temperature 01
03
80
AE
00
02
8C
2A
Alarm
01
03
80
B0
00
02
EC
2C
All values
01
03
80
A4
00
0E
AC
2D
Excample for the request:
Temperature 01
03
80
AE
00
02
8C
2A
Excample-answer = 1760,00
Temperature 01
03
04
44
DC
00
00
2F
39
4Byte
Byte1
Byte2
Byte3
Byte4
Summary of Contents for GSM
Page 10: ...METROTEC 10 4 3 Sketch of the ducting system ...
Page 15: ...METROTEC 15 ...
Page 16: ...METROTEC 16 ...