DL7, DL7L
95
16
MODBUS RTU / MODBUS TCP TRANSMISSION PROTOCOL
16.1 General information
Process values and totalizers are available as
holding
registers
and
input
registers
. It is
only possible to read the data.
16.1.1 Data types
uint/int
16bit
Reg
(Bit 15…0)
HByte
LByte
2.
1.
uint/int/float
32bit
Reg_L (Bit 15…0)
Reg_H (Bit 31…16)
HByte
LByte
HByte
LByte
2.
1.
4.
3.
uint/int/float
32bit sw
Reg_H (Bit 31…16)
Reg_L (Bit 15…0)
HByte
LByte
HByte
LByte
4.
3.
2.
1.
int/double
64bit
Reg_L (Bit 15…0)
Reg_H (Bit 31…16) Reg_L (Bit 47…32) Reg_H (Bit 63…48)
HByte
LByte
HByte
LByte
HByte
LByte
HByte
LByte
2.
1.
4.
3.
6.
5.
8.
7.
16.2 Registers addresses
Process values are available in the floating-point format as per IEEE-754 for the 32-bit
digit type with the floating point and single precision (32-bit floating point single).
The totalizers are available in the floating-point format as per IEEE-754 for the 64-bit
digit type with the floating point and double precision (64-bit floating point double).
16.2.1 Addresses table of Process values
No. measuring
channel
Register number
Modbus address
Size
(in registers)
1
300000 / 400000
00
2 (32bit float)
2
300002 / 400002
02
2 (32bit float)
…
…
…
…
…
…
…
…
99
300196 / 400196
196
2 (32bit float)
100
300198 / 400198
198
2 (32bit float)