DL7, DL7L
47
Input resistance
12
±10%
Maximum input voltage
± 40 VDC
Input protection
Polymer fuse 50 mA
Transducers powered from device:
module IN6I(24V)
module IN6I
24 VDC ±15% / max 0.25 mA
None
Galvanic separation from the other circuits
250 VAC; 1500 VAC for 1 minute
Galvanic separation between channels
None
(2)
In the device, it is possible to install max 4 modules with power output 24 VDC at the same time -
IN6I(24V).
IN6RTD; IN3RTD
– RTD / R input type module
Number of inputs:
module IN6RTD
module IN3RTD
6
3
Sensor type
Resistive (refer the table below)
Linear resistance
Sensor connection type
2-wire; 3-wire; 4-wire
Sensor current
200
A
Measuring range
0 .. 4000 Ω
Resolution
0.05 Ω
Wire resistance compensation in the 3-wire connection Automatic
Wire resistance correction in the 2-wire, 3-wire,
4-wire connection
Constant within the range of
–99.99 .. +99.99
Maximum resistance of the sensor wires
20
Maximum input voltage
± 40 VDC
Galvanic separation from the other circuits
250 VAC; 1500 VAC for 1 minute
Galvanic separation between channels
None
IN6TC
– mV type input module
Number of inputs
6
Sensor type
Thermocouple (refer the table below)
Linear voltage source
Measuring range
-140 .. +140 mV
Resolution
0.01 mV
Cold junction compensation
Any other temperature measuring channel (in
°C/°F) or a constant value,
Internal
sensor
measurement:
accuracy
±2.5 ⁰C (value can be calibrated by the user),
For thermocouple B
– no compensation
Maximum input voltage
± 40 VDC
Galvanic separation from the other circuits
250 VAC; 1500 VAC for 1 minute
Galvanic separation between channels
None
IN6V
– voltage type input module
Number of inputs
6
Sensor type
0-10 V (2-10 V, 0-5 V, 1-5 V)
Linear voltage source
Measuring range
-10 .. +10 VDC (or sub-range)
(the actual range -11 .. +11 VDC)
Resolution
0.0001 V