6
A
185mm
B
36
0mm
17
0mm
55
0mm
59
5mm
65
0mm
Refer
Chart
Firebox Model
A
B
Width
LTD Insert
500mm
405mm
560mm
Fascia Model
Base Width
Body Width
Trend
810mm
810mm
Insert Raised
LTD Insert
0mm
455mm insulated
10mm
455mm insulated
15mm
445mm insulated
20mm
436mm insulated
25mm
424mm insulated
30mm
408mm insulated
35mm
396mm insulated
40mm
366mm insulated
41mm & above
350mm insulated
45mm
50mm & above
Minimum Floor Protector projection and type
Diagram 4
Floor protector requirements
Metro fireplace inserts are designed to be installed direct
onto a concrete base. An insulated floor protector is required
to project in front of the Metro and must extend a minimum
of 200mm to each side of the door opening, making the
minimum floor protector width 825mm. The minimum floor
protector projection forward of the Metro is dependant on the
height of the fireplace insert above the combustible floor. The
following schedule of floor protector projections is measured
from behind the Metro fascia being the total floor protector
depth as shown in Diagram 4 below. Note, the heights
specified above the combustible floor can be achieved by: -
• The thickness of the floor protector
• Or by raising the fireplace insert
• Or a combination of the two
Wetbacks
The Metro LTD Insert can be fitted with either of Pioneer’s 3kW
or 4kW wetback option. Only Pioneer’s cast jacket wetback
system as illustrated on page 9 of this manual should be fitted
to a Metro. Alternative wetbacks will void the Metro’s emission
approvals and may seriously effect the performance of the
appliance and will void the owners warranty.
Both 3kW and 4kW wetback options can be fitted to either side
of the firebox, with the connection pipe heights illustrated in
Diagram 4 above, please note: -
• It is recommended the return pipe has a minimum rise of
1 in 12. Performance will reduce as the distance to the
storage cylinder increases.
• The wetback must be connected to a vented system. To fit
the wetback proceed as follows: -
1. Remove the brick from the inside of the firebox from the
side the wetback is to be fitted too.
2. Expose the holes in the firebox through which the
connection pipes will pass.
The LTD Insert has a 3mm pressed washer covering these
two openings and two 6mm bolts which are fitted inside
the firebox near the connection holes, remove these also.
3. Using a hole saw or snips, prepare the cabinet for the
connection pipes. Note, these holes should be a neat
fit or have any excess gap covered or filled with high
temperature insulation.
4. Using the tube of sealant supplied with the wetback, apply
a liberal bead of sealant around both connection holes on
the inside of the firebox. On the rear of the wetback casting
apply the remaining contents of the tube equally around
both connection pipes and also the outer circumference
of the wetback which will face the inside rear wall of the
firebox. This will completely seal the wetback to the inside
rear wall of the fire on installation.
5. Fit the wetback into the firebox and position the connection
pipes through the connection holes in the firebox.
6. Fit two bolts through the slots provided in the wetback, align
the wetback so its front edge is parallel to the door opening
& secure the bolts. The wetback is ready for connection to
the storage cylinder by a registered plumber.
Summary of Contents for LTD Insert