3. POSITIONING
The installation site should be equipped with a power supply of 220-240V and 50 Hz.
The power supply and the hydraulic system must comply with the local regulations.
The unit should be placed vertically, with a maximum inclination of 1°. The unit must be
well balanced and stable on the ground surface. Use the built-in adjustable pads to
level the unit.
The unit must be installed as close as possible to the hydraulic system in order to mini-
mize heat losses in the water pipes. The water pipe outlet should be insulated for the
same reason.
The unit should not be placed in direct contact with the sunlight.
The unit can only be installed in a frost-free room and it should follow the criteria:
• Room temperature between 5°C and 35°C.
• Drain possibility for condensate and floor drain.
• Solid base (approx. 500 kg / m
2
).
• It is necessary to ensure that there is sufficient space around the unit for mainte-
nance and service. A clearance of 0,5 m around the unit is recommended.
Once the appliance is located in the right position, remove the packaging and remove
the unit from the pallet.