Code
Set point
name
Description
Range
Factory
setting
D26
Extra
function*
The desired extra function is selected here. The
possible functions are Solar, Floor or Cooling.
Once the function is activated, move to the func-
tion menu and adjust the set point as desired.
OFF/
Solar/
Floor/
Cooling
OFF
D27
OFF
The SG ready function can be activated by the
installer here. Three possible modes can be select-
ed. This function allows the start of the heat pump
from an external access (See QA1 in Figure 16).
SG ready is not active if there is not external input
(SG1 OFF, SG2 OFF).
OFF/
SG Boost/
SG Eco/
SG Block
OFF
(SG
BOOST)*
The heat pump and electric heater must start, if
below the max water temperature allowed in the
tank. Both Heat Pump and Electric heater are
forced to operate (SG1 ON and SG2 ON).
(SG
ECO)*
The heat pump operates minimizing
costs, only the heat pump is activated ( SG1 OFF,
SG2 ON).
(SG
BLOCK)*
The unit can be stopped even if there is a need for
hot water (SG1 ON, SG2 OFF).
D28
Cooling
1*
The fan and heat pump runs until the additional
temperature T5 placed in the room environment is
below a certain level. The water temperature can
only reach the maximum temperature allowed in
the tank D33 (T HP max). The cooling function ac-
tivates a three-way damper, which directs the cold
exhaust air to a room with cooling requirements.
The two functions operate the damper in opposite
directions.
Cooling 1 (2). If the T5 is higher than B10 T
Cooling, the extra relay that operates the damper
(GP1) switches ON (OFF).
If the T5 is lower than B10 (T Cooling), the extra
relay that operate the damper (GP1) switches OFF
(ON).
Cooling1/
Cooling2
Cooling
1
Cooling
2*
SG Ready
Cooling T
ype