MI 3122 Smartec Z Line-Loop / RCD
Appendix A – Fuse table
52
Fuse type B
Rated
current
(A)
Disconnection time [s]
35m 0.1 0.2 0.4 5
Min. prospective short- circuit current (A)
6
30 30 30 30
30
10
50 50 50 50
50
13
65 65 65 65
65
15
75 75 75 75
75
16
80 80 80 80
80
20
100 100 100 100
100
25
125 125 125 125
125
32
160 160 160 160
160
40
200 200 200 200
200
50
250 250 250 250
250
63
315 315 315 315
315
Fuse type C
Rated
current
(A)
Disconnection time [s]
35m 0.1 0.2 0.4 5
Min. prospective short- circuit current (A)
0.5
5
5
5
5
2.7
1
10
10
10
10
5.4
1.6
16
16
16
16
8.6
2
20
20
20
20
10.8
4
40
40
40
40
21.6
6
60
60
60
60
32.4
10
100
100
100
100
54
13
130
130
130
130
70.2
15 150
150
150
150 83
16
160
160
160
160
86.4
20
200
200
200
200
108
25
250
250
250
250
135
32
320
320
320
320
172.8
40
400
400
400
400
216
50
500
500
500
500
270
63
630
630
630
630
340.2
Fuse type K
Rated
current
(A)
Disconnection time [s]
35m 0.1 0.2 0.4
Min. prospective short- circuit current (A)
0.5
7.5 7.5 7.5 7.5
1
15
15
15
15
1.6
24
24
24
24
2
30
30
30
30
4
60
60
60
60
6 90 90 90 90
10
150
150
150
150
13
195
195
195
195
15 225 225 225 225
16
240
240
240
240
20
300
300
300
300
25
375
375
375
375
32
480
480
480
480