MI 3102(H) BT
Eurotest
XE
Measurements
67
First fault leakage current measuring procedure
Select the
ISFL
function from the
OTHERS menu
.
Enable and set
limit
value (optional).
Connect
3-wire test lead or mains measuring cable to the instrument and tested
installation (see Figure 5.54 and Figure 5.55).
Press the
TEST
key to start measurement.
Store
the result by pressing the
MEM
key (optional).
Figure 5.56: Examples of measurement results for the first fault leakage current
Displayed results:
Isc1
.......... first fault leakage current at single fault between L1/PE
Isc2
.......... first fault leakage current at single fault between L2/PE