A 1588   

                               

            

 Multi range AC current clamps  

 

 

Description of current clamps 

 

The A 1588 multi range current clamps are designed for measuring alternating currents on low 
and medium power installations: 50 

mA ÷ 50 A.  

They have electronic module, and can be connected only to Metrel PowerQ series of measuring 
instruments:  
 

  Energy Master (MI 2883) 

  Master Q4 (MI 2885) 

  Power Master (MI 2892) 

 
Clamps  have  three  current  ranges  0.5A,  5A  and  50A,  which  are  selected  directly  by  the 
connected  instrument.  Embedded  electronic  module  is  powered  directly  from  the  connected 
instrument and does not need any additional power supply. 

 
The current transducer is housed in a plastic case that maintains double insulation as defined in 
Main parts of the current clamps are shown on figure bellow: 
 

 

1.  handles, 
2.  safety barrier, 
3.  conductor opening, 
4.  clamps jaw, 
5.  cable connection with 

connector. 

 

 
 

 

 

Figure 1: Multi range AC current clamps 

 

Summary of Contents for A 1588

Page 1: ...Multi range AC crrent clamps 0 5A 5A 50A A 1588 Instruction manual Version 1 0 Code no 20 752 829...

Page 2: ...el metrel si 2018 METREL Mark on your equipment certifies that this equipment meets the requirements of the EU European Union concerning safety and electromagnetic compatibility regulations No part of...

Page 3: ...MENT 7 POWER MEASUREMENT 8 LEAKAGE CURRENT MEASUREMENT 8 Measurement Of Leakage Current By Direct Method 8 Measurement Of Differential Current And or Current Difference 8 Determining Problems In Light...

Page 4: ...be touched during measurement Symbol on the current clamp indicates the possibility of a hazardous live condition if the operator ignores the required safety measures If the current clamps are used i...

Page 5: ...885 Power Master MI 2892 Clamps have three current ranges 0 5A 5A and 50A which are selected directly by the connected instrument Embedded electronic module is powered directly from the connected inst...

Page 6: ...Master MI 2892 Step 2 Switch on the measuring instrument Set Smart clamps and range on instrument s measuring setup For further information see Instruction manual of measuring instrument Step 3 Clamp...

Page 7: ...rrent primary current Is Measured current current transformer secondary current N2 Number of secondary turns N2 1000 U I Output voltage as function of current U k Im Factor k depends on selected curre...

Page 8: ...e active embraced conductors If no current is leaking to earth the sum of the currents passing through active conductors must be exactly zero regardless of the load currents If a leakage current is fl...

Page 9: ...ve them to dry totally before using it Do not use liquids based on petrol or hydrocarbons Do not spill cleaning liquid over the current clamps To clean jaw cut surfaces use slightly oiled soft cloth S...

Page 10: ...Frequency range 40 Hz 700 Hz 0 50 phase error 700 Hz 2500 Hz 30 phase error Continuity of measurements 100 A continuous 120 A 40 min 20 min intermitted Load impedance 1 k Working voltage 600 Vrms Inf...

Page 11: ...and industrial use Immunity Intended for use in industrial locations but can also be used for domestic purposes Performance criteria B with addition to the tables bellow Table 1 Immunity to radiated...

Reviews: