Flex current clamps A 1446
9
5 Measuring current with A 1446
I
1
2
Picture 5.1: Wrap the measured cable with the measuring clamp
To use the A 1446 Flexible Current Clamps, follow these instructions:
1. Connect the D01 3 Pin connector of the A 1446 Flexible Current Clamps to the
desired input on the measuring instrument (power meter,..).
2. Select the corresponding sensitivity (.. mV/A) on your instrument.
3. Wrap the flexible measuring head around the conductor to be tested, close coupling
(See Picture 5.1 ).
4. It is very important that the conductor is as the center and perpendicular to the
measuring head. (if it is no possible additional error of 2% of full scale can occur).
5. Do not measure close to other current-carrying conductors if possible. (An external
field of 40 A/m can cause an additional measurement error of 1% of full scale).
6. Make sure that the arrow marked on the clamp coupling points toward the correct
orientation for correct phase. (See Picture 5.1 )
7. Keep the clamp coupling more than 2.5 cm (1 inch) away from the conductor to be
tested and other nearby conductors.
8.
Observe the current value and waveform on the instrument’s display. If desired,
select the lower range on the measurement instrument.
Summary of Contents for A 1446
Page 1: ...Flex current clamps A 1446 User Manual Version 1 6 Code No 20 752 346...
Page 13: ...A 1446 13 9 A 1446 A 1446 60 A 600 A 6000 A A 1446 1446 A 1446 A 1446...
Page 14: ...A 1446 14 10...
Page 15: ...A 1446 15 11 1000 AT III 600 AT IV 30 1000...
Page 17: ...A 1446 17 12 Metrel...
Page 18: ...A 1446 18 13 A 1446 I 1 2 13 1 A 1446 9 3 D01 A 1446 10 11 5 1 12 2 13 40 1 14 5 1 15 2 5 1 16...
Page 19: ...A 1446 19 14 1446 A 1446...
Page 22: ...A 1446 22 25 C 15 C...