A 1398 PQA Iron Current Clamp
Inspection, Cleaning, Service & Calibration
8
4
Inspection
To maintain operator safety and ensure reliability of the A 1398 PQA Iron Current Clamp, it is
good practice to inspect it on a regular basis. Check that the enclosure and optional connection
are without defects such as scratches or breaks.
Jaw surface must be clean. Pollution on jaw surfaces reduces the current clamp sensitivity.
5
Cleaning
No special maintenance is required for the housing. To clean the surface of the A 1398 PQA use
a soft cloth slightly moistened with soapy water or alcohol. Then leave the A 1398 PQA to dry
totally before use.
Warnings:
❑
Do not use liquids based on petrol or hydrocarbons!
❑
Do not spill cleaning liquid over the A 1398 PQA!
6
Service and Calibration
It is essential that your clamp is regularly calibrated in order to guarantee the technical
specification listed in this Instruction manual. We recommend 2-year calibration interval. Metrel
encloses an original calibration certificate with every new instrument and clamp.
For recalibration and repairs under or out of warranty time please contact your distributor for
further information.
Warning:
❑
Only a competent, authorized person is allowed to carry out service intervention!