Locker Controller ELS NET Technical Manual
Signalization:
“EOPn” is displayed and all lockers
connected to the Locker Controller start to unlock and
open one after another and corresponding locker
numbers are displayed.
NOTE:
To stop the emergency unlocking procedure press
the Emergency open pushbutton again.
Device replacement
This chapter describes Locker Controller replacement procedure. The problem should be identified
before any repairing is tried.
STEP 1:
Disconnect the power supply.
NOTE
Disconnect the adapter not the wires fixed on the Locker Controller board to avoid short circuit.
STEP 2:
Open the Locker Controller Box/Locker (see Locker manufacturer's documentation).
STEP 3:
Disconnect all cables and
mark their exact position.
STEP 4:
On the new Locker Controller set the same network address.
STEP 5:
Replace the Locker Controller with a new one.
STEP 6:
Reconnect all cables
exactly the same as they were connected previously
.
STEP 7:
Connect the power supply.
STEP 8:
Press the parameters request “PARRQ” button to download operating parameters as they
were on the previous Locker Controller.
STEP 9:
Close the Locker Controller Box/Locker (see Locker manufacturer's documentation).
Maintenance
No special maintenance is needed.
The maintenance people should check the device operation at least once a year.
NOTE
Direct spraying or splashing water can cause damage to Locker Controller or Electric Locks!