Locker Controller ELS NET Technical Manual
Test mode activation
STEP 1:
With small flat headed screwdriver or similar tool
set switches 1 to 4 located on the “Operating mode DIP
switch” to ON (switch up).
STEP 2:
Connect the ELS NET Tester to the Locker Controller as described in the paragraph
“ELS NET
Tester connection”
.
STEP 3:
Power-off and back on the Locker Controller to activate the Test mode.
STEP 4:
Shortly after power on, numbers from “0.0.0.0.”
to “9.9.9.9.” are displayed. This indicates that the Test
mode of operation is activated.
NOTE:
To return to Normal mode of operation set the switches 1 to 4 back to OFF (switch down) and
power-off and back on the Locker Controller.
Erasing operating parameters
Operating parameters can be erased (initialized to default values) only in Test mode of operation.
STEP 1:
Before powering-up the Locker Controller in Test
mode, both pushbuttons (Emergency open and
Parameters request) should be pressed and hold for 3
seconds after power up.
Operating parameters are erased.
Upon buttons release, Test mode of operation is
activated.