Locker Controller ELS NET  Technical Manual 

 

Test mode activation 

 

 

STEP 1:

 With small flat headed screwdriver or similar tool 

set switches 1 to 4 located on the “Operating mode DIP 
switch” to ON (switch up). 
 
 

 

STEP 2:

 Connect the ELS NET Tester to the Locker Controller as described in the paragraph 

“ELS NET 

Tester connection”

 
STEP 3: 

Power-off and back on the Locker Controller to activate the Test mode. 

 

 

STEP 4:

 

Shortly after power on, numbers from “0.0.0.0.” 

to  “9.9.9.9.”  are  displayed.  This  indicates  that  the  Test 
mode of operation is activated. 

 

NOTE:

 To return to Normal mode of operation set the switches 1 to 4 back to OFF (switch down) and 

power-off and back on the Locker Controller. 
 
 

 Erasing operating parameters 

 
Operating parameters can be erased (initialized to default values) only in Test mode of operation. 
 

 

STEP 1: 

Before powering-up the Locker Controller in Test 

mode,  both  pushbuttons  (Emergency  open  and 
Parameters  request)  should  be  pressed  and  hold  for  3 
seconds after power up.  
Operating parameters are erased. 
Upon  buttons  release,  Test  mode  of  operation  is 
activated. 

 
 
 

Summary of Contents for ELS NET LC08

Page 1: ...Locker Controller ELS NET Technical Manual...

Page 2: ...d 9 Metra NET Network connection Locker Controller without distribution board 10 Metra NET Network connection Locker Controller with distribution board 10 External emergency open pushbutton connection...

Page 3: ...Page 3 Locker Controller ELS NET Technical Manual Device replacement 22 Maintenance 22 Troubleshooting Guide 23 Technical data 23 Appendix 23...

Page 4: ...art of this manual may be reproduced in any form or by any means without prior written permission of Metra in eniring d o o The contents of this manual are subject to change without notice All efforts...

Page 5: ...is distributed over Metra NET Network to Metra user interface devices and over Metra Network Controller to LAN WAN and Metra software For easier installation on site different configurations of contro...

Page 6: ...k 10 36 Local CAN 11 Electronic Lock 11 37 Local CAN 12 Electronic Lock 12 38 BDM Loader 13 Electronic Lock 13 39 COM Not used 14 Electronic Lock 14 40 Local CAN 15 Electronic Lock 15 41 Local CAN 16...

Page 7: ...xtension Modules When Locker Controller without mounting plate is used connect up to two Extension modules by 6 wire flat cable There are two equivalent connectors on the main electronics board LC16A...

Page 8: ...Controller without distribution board Regulated 12 VDC power supply is required for proper operation Connect as many units as possible to a single power supply unit Consult the Technical Specificatio...

Page 9: ...nsult the Technical Specifications section of this document for current consumption Connect 12V DC regulated power supply to designated terminals The terminals are marked as 12V for positive connectio...

Page 10: ...ne Terminator must be connected at the far end of the network cable See also Metra NET Network Installation Manual for different wiring schemes Connect the twisted pair network cable to designated ter...

Page 11: ...er ELS NET Technical Manual External emergency open pushbutton connection optional Connect the blue and blue white wires of the UTP cable from the Emergency open pushbutton to designated terminals as...

Page 12: ...nnection optional Connect the 6 pole flat cable to the connector marked I2C connector as shown in the schematic DIP switch settings description description 1 Emergency open pushbutton 3 Network Addres...

Page 13: ...must be unlocked via external or internal emergency open pushbutton NOTE Network based functionality will be present only if the server is running and the Locker Controller has been properly configur...

Page 14: ...0 0 1 1 0 1 1 28 1 0 0 1 1 0 1 78 0 0 1 1 1 0 0 29 1 0 0 1 1 1 0 79 0 0 1 1 1 0 1 30 1 0 0 1 1 1 1 80 0 0 1 1 1 1 0 31 1 0 1 0 0 0 0 81 0 0 1 1 1 1 1 32 1 0 1 0 0 0 1 82 0 1 0 0 0 0 0 33 1 0 1 0 0 1 0...

Page 15: ...pplied the following LEDs are on Yellow LED on Locker Controller 12VDC present Green LED on Locker Controller 5VDC regulated on board active Yellow LED on Extension Module s 12VDC present Green LED on...

Page 16: ...er is transmitting data packets to Metra NET Network Setting Operational parameters via Metra NET Network Metra Network Controller must be connected to Metra NET Network Metra server must be running a...

Page 17: ...n 1 Internal Emergency open pushbutton STEP 1 Press the Emergency open pushbutton All lockers connected to the Locker Controller start to unlock and open one after another External Emergency open push...

Page 18: ...umbers from 0 0 0 0 to 9 9 9 9 are displayed This indicates that the Test mode of operation is activated NOTE To return to Normal mode of operation set the switches 1 to 4 back to OFF switch down and...

Page 19: ...e locker door STEP 2 Locker index 1 32 as it is connected to the Locker Controller is displayed STEP 3 Locking time in milliseconds is displayed shortly after locker index Locking time should be betwe...

Page 20: ...nlocking time in milliseconds is displayed shortly after locker index Unlocking time should be between 150 and 300 NOTE You can repeat this procedure on all lockers connected to Locker Controller boar...

Page 21: ...ameters request pushbutton test press leftmost pushbutton bellow the 4 digit LED display on the ELS NET Tester Testing Emergency open pushbutton Internal Press the Emergency open pushbutton External T...

Page 22: ...2 Open the Locker Controller Box Locker see Locker manufacturer s documentation STEP 3 Disconnect all cables and mark their exact position STEP 4 On the new Locker Controller set the same network addr...

Page 23: ...wo extension modules 2 A peak 1 A average Operating temperature range 0 to 50 C Audio signal integrated piezoelectric beeper Buffer capacity 40 records Electronic Lock Interface Up to 16 24 32 El Lock...

Page 24: ...NET Physical dimensions Locker Controller Locker Controller Extension Module 1 2 5 3 4 6 7 8 1 2 5 3 4 6 7 8 19 179 100 7 5 15 8 5 17 7 5 26 5 8 5 37 5 36 75 5 84 5 1 2 3 4 11 89 16 39 5 44 5 8 5 100...

Page 25: ...Appendix 2 Locker Controller ELS NET 79 5 5 94 20 4 0 3 4 2 1 6 4 5 Physical dimensions Mounting rails 1 2 5 3 4 6 7 8 1 2 5 3 4 6 7 8 180 79...

Page 26: ...Appendix 3 Locker Controller ELS NET Physical dimensions Mounting plate 5 8 39 39 46 5 368 380 8 4 4 2 368 6 4 2 10 171 159 115 78 46 5 366...

Page 27: ...rk LAN Reception 2 Metra DB Server Reception 1 Appendix 4 Locker Controller ELS NET Network schematic Locker Controller 2 Network Controller TCP IP Master Emergency open push button Max 32 lockers Max...

Page 28: ...s 1 2 3 4 1 2 3 4 141 143 142 144 145 146 147 150 151 152 153 154 155 160 159 161 162 163 164 167 168 169 170 171 172 156 157 165 166 148 149 158 172 143 141 142 Appendix 5 Locker Controller ELS NET D...

Reviews: