Installation Guide—DX LCD Display
9
Table 2: Dedicated Areas of the Display Screen
Area
Description
Name of Display
Configuration
The name of the display configuration that the
DX LCD Display is currently using. You define the
name when you create the display configuration in
the GX-9100 software configuration tool.
Time
The current time in the connected DX controller in
either 12 or 24 hour format, as defined in the display
configuration.
More . . .
More is displayed on the next to last line of the
display if there are more pages of data associated
with the current function. Use the
(Page Up) or
(Page Down) key to display the next or previous
page.
ALARM: Most Recent Alarm
The active alarm that occurred most recently and its
status.
Total: # Alarms
The number of points that are currently in an alarm
state.
The Keypad
Table 3 describes the keypad keys and symbols, and Table 4 describes
the LED indicator located in the center of the keypad.
Table 3: Keypad Keys
Name
Symbol
Description
Up / Down
These keys allow you to move between lines on a
page, for example to move the selection bar though
different items in a menu.
Page Up /
Page Down
These keys allow you to scroll between pages if
more than one screen of information is available for
the selected function. This is indicated by the
prompt “More...” in the bottom right hand corner of
the screen
Plus / Minus
These keys allow values to be changed (increased
or decreased) while in edit mode. If either of the
keys is held down, then the auto-repeat function
allows you to obtain the value you require without
having to use multiple keystrokes.
Escape
esc
This key is used to leave or abort a menu/sub-menu
or adjust/command procedure
Enter
The enter key is used to confirm an action, for
example when choosing a menu option or
commanding/adjusting a value.
Table 4: Keypad Indicator
Name
Symbol
Description
Alarm
Indicator
!
In addition to the audible alarm, a red LED
positioned above this symbol in the center of the
keyboard membrane indicates whether alarms are
present in the monitored system, as follows:
Flashing
At least one unacknowledged alarm.
Steady On
Alarms are present but all have been
acknowledged.
Off