Metal Fab AL29-4C Installation Instructions Manual Download Page 5

5

PLATE SUPPORT ASSEMBLY

The Plate Support Assembly is designed to provide support to vertical and 

horizontal sections. The Plate Support must be attached to the building structure 

or support with rigid structural members. Proper clearance to combustible 

construction must be maintained.
For maximum support, attach the entire perimeter of the Plate Support Assembly 

to the structural framing. (See 

FIG. 5

). Structural members are supplied by the 

installer. The Flange Band is placed between the Support Plate and the Clamp 

Rings and aligned with notches for the Flange Band Clamps. Align holes of 

the support plate and Clamp Rings and assemble together using the hardware 

provided.

Vertical vent systems can be suspended pre-assembled and lowered into 

a shaft. Refer to 

TABLE 5

 for maximum height that can be suspended from 

overhead. 

Do not

 pre-assemble in the horizontal position and raise to the 

vertical position for installation.

WARNING:  ALL JOINTS MUST BE PROPERLY ASSEMBLED 

AND ALLOWED TO CURE BEFORE LIFTING FOR 

INSTALLATION.

WALL PENETRATION

1.

  Prior to installation, determine proper location of wall thimble so that 

a minimum slope of 1/4” (6mm) per foot is maintained in the  

horizontal section of vent to ensure proper flow of condensation.

2.  Prepare the wall by cutting a square opening per 

TABLE 6

. (Opening  

size adequate to insert Wall Thimble components)

3.  Install the Wall Thimble by inserting the larger of the two parts  

on the appliance (interior) side. 

4.  Next, apply a bead of sealant around the edges of the 

 

exterior (smaller of the two parts) Wall Thimble component. Then  

install this part of the Wall Thimble by inserting the smaller collar into  

the other component from the previous step.

NOTE:  The two horizontal cylinders of the Thimble must engage a  

 

 

minimum of two inches.

5.  Fasten both sides of the Wall Thimble using screws or nails.
6.  Once the Thimble is installed, Corr/Guard vent pipe can be inserted 

into the Thimble. For 3” - 5” diameter Corr/Guard insert the male  

end first. (See 

FIG. 6, 7 & 8

). 

7.  Assemble Corr/Guard vent from the Wall Thimble section back to the 

appliance.

8.  Install a horizontal termination to complete the assembly.
9.  Once assembly is completed, apply a bead of high-temp sealant  

around the pipe and the exterior plate of the Thimble to protect  

against weather.

TABLE 5

Height

Diameter

FCSSW

FCS

FCS-1

FCS-2

  6”(152mm)

229’(70m)

75’(23m)

62’(19m)

55’(17m)

  7”(178mm)

215’(66m)

70’(21m)

58’(18m)

52’(16m)

  8”(203mm)

200’(61m)

70’(21m)

58’(18m)

52’(16m)

  9”(229mm)

190’(58m)

60’(18m)

49’(15m)

44’(13m)

10”(254mm)

175’(53m)

60’(18m)

49’(15m)

44’(13m)

12”(305mm)

145’(44m)

50’(15m)

41’(15m)

37’(11m)

14”(356mm)

120’(37m)

50’(15m)

41’(15m)

37’(11m)

16”(406mm)

120’(37m)

50’(15m)

41’(15m)

37’(11m)

18”(105mm)

105’(32m)

45’(14m)

37’(11m)

33’(10m)

20”(508mm)

105’(32m)

45’(14m)

37’(11m)

33’(10m)

22”(559mm)

  95’(29m)

40’(12m)

33’(10m)

30’( 9m)

24”(610mm)

  90’(27m)

40’(12m)

33’(10m)

30’( 9m)

26”(660mm)

  90’(27m)

50’(15m)

40’(12m)

40’(12m)

28”(711mm)

  90’(27m)

40’(12m)

40’(12m)

30’( 9m)

30”(762mm)

  80’(24m)

40’(12m)

40’(12m)

30’( 9m)

32”(813mm)

  80’(24m)

40’(12m)

30’(  9m)

30’(  9m)

34”(864mm)

  70’(21m)

40’(12m)

30’(  9m)

30’(  9m)

36”(914mm)

  70’(21m)

30’(  9m)

30’(  9m)

30’(  9m)

FIG. 5

FLUE

CASING

FLANGE BAND

CLAMP RING

PLATE

STRUCTURAL BRACING 

(BY OTHERS)

FIG. 6

2” MIN. 

OVERLAP

OUTSIDE BUILDING 

SURFACE

SEALANT

INSIDE BUILDING 

SURFACE

WOOD STUD

TO TERMINATION

TO APPLIANCE

WALL THIMBLE INSTALLATION 

3”- 5” (76mm-127mm) CGSW

FIG. 7

WALL THIMBLE INSTALLATION 

3”- 5” (76mm-127mm) CG

SEALANT

CASING END CLOSURE

TERMINATION

TO APPLIANCE

FIG. 8

WALL THIMBLE INSTALLATION

6”- 36” (152mm-914mm) FCSSW, FCS, FCS-1 & FCS-2

CASING END 

CLOSURE

TERMINATION

SEALANT

RADIATION 

SHIELD 

(SINGLE WALL)

Summary of Contents for AL29-4C

Page 1: ...E INSTRUCTIONS VERY CAREFULLY EXAMINE ALL COMPONENTS FOR POSSIBLE SHIPPING DAMAGE BEFORE INSTALLATION PROPER JOINT ASSEMBLY IS ESSENTIAL FOR A SAFE INSTALLATION FOLLOW THESE INSTRUCTIONS EXACTLY AS WR...

Page 2: ...y dwellings a venting system that extends through any zone above that on which the connected appliance is located shall be provided with an enclosure having a fire resistance rating equal to or greate...

Page 3: ...e joint NOTE If the seal gasket pushes out of the groove during the assembly process apply a light film of synthetic based lubricant to the top surface of the gasket or spray a light film of soapy wat...

Page 4: ...THODS PIPE DIAMETER MODEL MAXIMUM HEIGHT PLATE SUPPORTS 3 5 76mm 125mm CG CGSW 30 9 1m 6 12 152mm 305mm FCS 50 15 2m 6 12 152mm 305mm FCS 1 41 12 5m 6 12 152mm 305mm FCS 2 37 11 3m 6 12 152mm 305mm FC...

Page 5: ...e smaller collar into the other component from the previous step NOTE ThetwohorizontalcylindersoftheThimblemustengagea minimum of two inches 5 Fasten both sides of the Wall Thimble using screws or nai...

Page 6: ...th specified by the appliance manufacturer s installation instructions Vertical terminations must terminate no less than 2 0 61m above the roof or any wall or vertical structure closer than 8 2 4m A v...

Page 7: ...RNING DO NOT PLACE ANY TYPE OF INSULATION IN ANY REQUIRED CLEARANCE SPACES SURROUNDING THE VENT SYSTEM GUY RING FCSGR Chimneys that exceed 5 above the roof or are installed in severe weather regions m...

Page 8: ...asing wall around the VL inner pipe section Secure the casing by installing 8x1 2 sheet metal screws at prepunched holes See FIG 17 P O Box 1138 WICHITA KANSAS 67201 316 943 2351 Fax 316 943 2717 2018...

Reviews: