INSTALLERS MANUAL  

SLIDING DOOR AUTOMATION 

 

(EN) 

 

 

 

SDA-04 

 

SDA-04DCB2 

 

MDA250 & MDA450  MDA120

 

 

(SW version 5.xx ) 

(SW version 22.0 ) 

 

 

 

Version

 

:

 

October 2017 

Reference

 

:

 

10.03.02  REV:03 

Type

 

:

 

Translation of the original Dutch document 

Order number  :  201060 

Summary of Contents for MDA120

Page 1: ...om Ambachtsstraat 11 www metaflexdoors nl 7122 MP Aalten INSTALLERS MANUAL SLIDING DOOR AUTOMATION EN SDA 04 SDA 04DCB2 MDA250 MDA450 MDA120 SW version 5 xx SW version 22 0 Version October 2017 Refere...

Page 2: ...e the user must obtain a new copy of the instruction manual from Metaflex Doors Europe BV 2017 Metaflex Doors Europe BV All rights expressly reserved Reprinting copying editing or republication and di...

Page 3: ...ans from Metaflex Doors Europe BV MDE or Metaflex certified personnel or authorised retailers hereafter referred to as distributor If this is not possible check with MDE for an authorised distributor...

Page 4: ...ollers 8 3 Description of the door and its control 9 3 1 Basic rail components 9 3 2 Basic door components 9 3 3 Controller connection information 10 4 Safety regulations 11 4 1 Mechanical safety regu...

Page 5: ...tionality 29 8 Parameter settings short version 30 8 1 Parameterlijst eind gebruikers 30 8 2 Parameterlijst installateurs 30 8 3 Conversion table parameters for installers 4 06 5 xx 33 9 Display codes...

Page 6: ...ual carefully so that it may be used for future reference at any time 1 2 Manufacturer Distributor Manufacturer Metaflex Doors Europe BV Ambachtsstraat 11 7120 AH Aalten The Netherlands www metaflexdo...

Page 7: ...activities unless specifically tasked and authorised Technician The technician is a Metaflex technician or a technician that has been provided with express written permission from Metaflex who is qua...

Page 8: ...complete configuration When opening the door using the handle the door will operate fullly automatically after a few centimetres adjustable As a result even the heaviest doors can be easily opened by...

Page 9: ...ponents 2 1 6 5 4 7 3 Legend 1 SDA 04 SDA 04DCB2 controller Display is visible from the door opening 2 Return wheel 3 Driver toothed belt tensioner 4 Reducer gearbox 5 AC motor equipped with pulse gen...

Page 10: ...n off switch 5 Input and output control 6 RS 232 port to be made use of by MDE Distributor technician 7 AC Motor pulse generator connector SDA 04DCB2 12 3 4 5 6 7 8 Legend 1 DC Motor pulse generator c...

Page 11: ...the wall frame and the recessed hand grip in the form of a cup on the inside of the door panel During closing Ensure that there are no obstacles in the door opening Beware of the potential crushing of...

Page 12: ...signal should be switched via a relay that is closely located to the SDA 04 controller Modifications to the SDA 04 controller are not allowed Modifications to the device can hamper the functioning and...

Page 13: ...outer ring of the connector must always be firmly screwed onto the controller tighten screws by hand do not use tools 1 In connection with EMC and electrical safety the device must not be switched on...

Page 14: ...d the ESC button is pressed Explanation of different SDA 04 terms Configuration process After switching on the power the SDA 04 determines its endpoints and the minimum power speed settings required t...

Page 15: ...losure Latch Electrical Mechanical balance lock Electrical lock operated by a magnetic latch Blocking by means of an electric motor interlock parameter setting Medical grounding conforming to NEN 3134...

Page 16: ...the monitoring of circuit breakers and all claims arising from the failure of a security switch will be rejected Protection devices on the door Various protection devices can be connected to the door...

Page 17: ...splayed The number to the left of the display shows the parameter number The number to the right shows the value that has been set 7 1 1 Viewing a parameter Once in the parameter menu you can view the...

Page 18: ...tays open until the next operation action t1 Pulse open pulse closed the door closes when Timer 1 has counted down to zero parameter 3 t2 Pulse open pulse closed the door closes when Timer 2 has count...

Page 19: ...n activated the door will only open to the maximum width for the passage of pedestrians parameter 5 despite being commanded to open fully For example during the winter in order to reduce heat loss whe...

Page 20: ...AC motor 370VA up to 440Kg 2 Configuring the controller to a Metaflex Type 3 AC motor 370VA up to 3000Kg Warning No parameter setting Code E08 in display Incorrect setting Code E13 in display Paramet...

Page 21: ...o a manual override condition and the door can be opened by hand and it will also travel to the partially opened position 2 The controller enters into a manual override condition and the door can be o...

Page 22: ...ill also work as an opener any interruption of the signal will open the door Parameter 42 0 Personal Safety 2 message PS3 in EN16005 mode input 32 Photocell 2 message 3 in Legacy mode 0 Only active wh...

Page 23: ...ile closing When this value is set to 9 the DMS is the same while the door is opening and closing 0 DMS value is 3 25 times greater while the door is closing 1 9 The difference factor between the MDS...

Page 24: ...aking distance slow close of the door value in cm which makes the door move more slowly 0 Function disabled 1 50 additional braking distance CM including lower speed Parameter 56 0 Extending the braki...

Page 25: ...ault 5 Monitoring function for controlling the operation of a safety device Sensor on input 29 6 Monitoring function for controlling the operation of a safety device Sensor on input 29 and 32 7 Interl...

Page 26: ...1 door cycle 0 In the event that the door has closed in a locked state input 1 and or 2 are active relay 1 will be activated Motor lock will stay idle 1 In the event that the door has closed in a lock...

Page 27: ...ct as an escape door The door will go to the 100 open position 2 In the event of a fire alarm the door will act as a fire door the door will go to the closed position all safety devices are disabled N...

Page 28: ...ter the door state On activation of either inputs 1 Lock or 2 One Way the door will close 3 Input is configured to act as a permanent toggle input fully open close In case of an opened door activation...

Page 29: ...ttention Each door must have a unique number if more than one door has the same number this will lead to conflicts in the software Parameter 91 0 Interlock Time 0 Normal interlock configuration no tim...

Page 30: ...Number of door movements Number of movements x100 0 9999 0 11 74 Number of power cycles The number of times power has been switched on and off 0 9999 0 12 69 Fault 1 laatste storing n code 0 13 70 Fa...

Page 31: ...Extra distance to run in slow mode measured in cm 0 50 0 56 86 Slow mode to end position Extra distance to run in slow mode measured in cm 0 50 0 57 78 Extra force during closing 0 Off 1 9 On 1 weak...

Page 32: ...nput 12 13 0 normal 1 open input 12 2 fully open 12 of semi open 13 open 3 emergency open inp 12 4 door open or close depending on position 5 1x press semi open 2x press during opening full open 0 1 2...

Page 33: ...h the introduction of the 5 xx and 22 00 software for the SDA 04 and SDA 04DCB2 some drastic changes in the parameter structure have been made In the overview below you can find a conversion table fro...

Page 34: ...e activated Hi Hi Input half open inside activated iLoc iL Input lock activated PS 1 Safety sensor 1 activated PS 2 Safety sensor 2 activated PS 3 Safety sensor 3 activated PS 4 Safety sensor 4 activa...

Page 35: ...ch Input 2 Any active electrical interlocks are lifted up Restore N C Input 4 Emergency stop operated Emergency stop is operated Input 6 or 1 Door assumes fire position Restore N C Input 5 Lock proble...

Page 36: ...and or errors SDA 04AC with 370 Watt AC motor at rest no current activities and or errors Meaning Clear message Controller low voltage fault Check mains supply reset Controller high voltage fault Chec...

Page 37: ...uts and outputs of the SDA 04 These signals are all provided on the two green connectors on the right side of the controller The chart below provides each input output terminal number the function nam...

Page 38: ...de User This input is used to bring the door to the Half open position or to allow the door to close in the event of a Pulse open Pulse close system When it is one_way the action is blocked 15 Open_in...

Page 39: ...afety inputs 29 and 32 Switch to 24VDC or 0VDC controller power supply Input signals Switch to 24VDC controller power supply Output signals relay Maximum 24 VAC DC 500mA Motors 90 Watt WDH250wpx 90W 3...

Page 40: ...ter switching on the version number will be displayed for 1 second The SDA 04 will meet the requirements for the versions in the table below SDA 04 Controller featuring EN16005 software Version Descri...

Page 41: ...Installers manual 10 03 02 R03 201058 EN SDA 04 SW 5 xx SDA 04DCB2 SW 22 00 Page 41 of 55 14 Connection examples...

Page 42: ...Installers manual 10 03 02 R03 201058 EN SDA 04 SW 5 xx SDA 04DCB2 SW 22 00 Page 42 of 55...

Page 43: ...Installers manual 10 03 02 R03 201058 EN SDA 04 SW 5 xx SDA 04DCB2 SW 22 00 Page 43 of 55...

Page 44: ...Installers manual 10 03 02 R03 201058 EN SDA 04 SW 5 xx SDA 04DCB2 SW 22 00 Page 44 of 55...

Page 45: ...Installers manual 10 03 02 R03 201058 EN SDA 04 SW 5 xx SDA 04DCB2 SW 22 00 Page 45 of 55...

Page 46: ...Installers manual 10 03 02 R03 201058 EN SDA 04 SW 5 xx SDA 04DCB2 SW 22 00 Page 46 of 55...

Page 47: ...Installers manual 10 03 02 R03 201058 EN SDA 04 SW 5 xx SDA 04DCB2 SW 22 00 Page 47 of 55...

Page 48: ...Installers manual 10 03 02 R03 201058 EN SDA 04 SW 5 xx SDA 04DCB2 SW 22 00 Page 48 of 55...

Page 49: ...Installers manual 10 03 02 R03 201058 EN SDA 04 SW 5 xx SDA 04DCB2 SW 22 00 Page 49 of 55...

Page 50: ...Installers manual 10 03 02 R03 201058 EN SDA 04 SW 5 xx SDA 04DCB2 SW 22 00 Page 50 of 55...

Page 51: ...Installers manual 10 03 02 R03 201058 EN SDA 04 SW 5 xx SDA 04DCB2 SW 22 00 Page 51 of 55...

Page 52: ...Installers manual 10 03 02 R03 201058 EN SDA 04 SW 5 xx SDA 04DCB2 SW 22 00 Page 52 of 55...

Page 53: ...Installers manual 10 03 02 R03 201058 EN SDA 04 SW 5 xx SDA 04DCB2 SW 22 00 Page 53 of 55...

Page 54: ...Installers manual 10 03 02 R03 201058 EN SDA 04 SW 5 xx SDA 04DCB2 SW 22 00 Page 54 of 55...

Page 55: ...Installers manual 10 03 02 R03 201058 EN SDA 04 SW 5 xx SDA 04DCB2 SW 22 00 Page 55 of 55...