SAFETY 

This heater is a self-contained infrared radiant ceramic heater. Safety information required during installation 
and operation of this heater is provided in this manual and the labels on the product. The installation, service 
and maintenance of this heater must be performed by a contractor qualified in the installation and service of 
gas fired heating equipment. 
All personnel in contact with the heater must read and understand  all safety information, instructions and 
labels  before  operation.  The  following  symbols  will  be  used  in  this  manual  to  indicate  important  safety 

information. 
 

 

Warning instructions must be followed to prevent or avoid hazards which 
may cause serious injury, property damage or death. 

 

 

 

Caution  instructions  must  be  followed  to  prevent  incorrect  operation  or 
installation  of  the  heater  which  may  cause  minor  injury  or  property 
damage. 

2) 

INSTALLER RESPONSIBILITY 

The installer is responsible for the following: 

 

The  heater  installation,  electrical  and  gas  supplies  must  be  installed  in  accordance  with  these 
installation instructions and any applicable codes and regulations. 

 

Every heater shall be located with respect to building construction and other equipment so as to permit 
access to the heater.  

 

Each installer must follow the clearances to combustible materials for the heaters. 

 

Install  the  heater  so  that  the  supports  and  hangers  are  correctly  spaced  in  accordance  with  these 
instructions. The heater must be supported by materials having a working load limit of at least 87lbs. 

 

Supply the owner with a copy of these Installation and Operation Instructions. 

 

Gravity or mechanical means shall be provided to supply and exhaust at least 4 CFM per 1,000 Btu/hr 
input of installed heaters. 

 

Never use the heater as a support for a ladder or other access equipment. Do not hang anything from the 
heater. 

 

Supply all installation materials necessary that are not included with the heater. 

 

Check the nameplate to make sure that the burner is correct for the gas type in the building. 

3) 

GENERAL INFORMATION 

 

This heater is a self-contained infrared radiant ceramic heater for use in locations where flammable gases or 
vapors are not generally present (as defined by OSHA acceptable limits) and is intended for the heating of 
nonresidential spaces.  
 

”For indoor installation only.  Not for 
use in residential dwellings.” 

«Installation à l’intérieur seulement.  Ne 
pas installer dans un logement.» 

 

 

 

 
 
 

Summary of Contents for R (B,S,M) D SERIES

Page 1: ...servicing this equipment In locations used for the storage of combustible materials signs must be posted to specify the maximum permissible stacking height to maintain the required clearances from the...

Page 2: ...the National Fuel Gas Code ANSI Z223 1 latest edition are available from the CSA at 8501 East Pleasant Valley Road Cleveland Ohio 44131 or 55 Scarsdale Road Don Mills Ontario M3B 2R3 All NFPA codes ar...

Page 3: ...regulations Every heater shall be located with respect to building construction and other equipment so as to permit access to the heater Each installer must follow the clearances to combustible mater...

Page 4: ...reas used for storage of combustible materials where they may be stacked below the heater NFPA54 requires that the installer must post signs that will specify the maximum permissible stacking height t...

Page 5: ...imum Clearances to Combustibles listed in the manual and on the heater at all times 4 MINIMUM CLEARANCES TO COMBUSTIBLES For maximum safety the building must be evaluated for hazards before installing...

Page 6: ...USTIBLES MODEL R B S M D Series Mounted Horizontally Mounted at 35 Angle Angle Mounting SIDES CEILING BELOW BELOW FRONT REAR w Standard Reflector w Reflector Extension w Standard Reflector w Reflector...

Page 7: ...S M D 140 N1C 140 000 4 41 n a 58 lbs 17 R B S M D 160 N1C 160 000 4 38 n a 58 lbs 18 R B S M D 033 L1C 33 000 1 n a 52 30 lbs 11 R B S M D 066 L1C 66 000 2 n a 52 35 lbs 13 R B S M D 100 L1C 99 000 3...

Page 8: ...the gas manifold assembly is on the lower side of the heater Coil chains No 2 or larger or rigid supports may be used to mount the heater which must be suspended from a permanent structure with adequa...

Page 9: ...ocated in accordance with the required clearances to combustibles below the heater as listed on the nameplate of the heater 3 Pipe joint compounds must be resistant to the action of liquefied petroleu...

Page 10: ...the heater must be released before proper heater operation 7 After all gas connections have been made make sure the heater and all gas outlets are turned off before the main gas supply is turned on Tu...

Page 11: ...stment is required remove the cover screw Using a small screwdriver turn the adjustment screw clockwise to increase or counter clockwise to decrease the gas pressure to burner Replace the cover screw...

Page 12: ...ve electrical circuit one that is not controlled by a light switch 4 The power supply to the unit should be protected with a fused disconnect switch or circuit breaker A service switch as required by...

Page 13: ...ATER PER THERMOSTAT B LINE VOLTAGE 120V THERMOSTAT CONNECTIONS MULTIPLE HEATERS PER THERMOSTAT C LOW VOLTAGE 24V THERMOSTAT CONNECTIONS MULTIPLE HEATERS PER THERMOSTAT POWER SUPPLIED FROM FAN CENTER R...

Page 14: ...and outlet vent area depending on height and temperature difference is as follows RD030 RD033 RD035 0 49 s f RD100 1 48 s f RD040 0 57 s f RD120 1 72 s f RD060 RD066 RD070 0 98 s f RD132 RD140 1 97 s...

Page 15: ...s before attempting to relight 6 The heater must be grounded Poor grounding will give nuisance lockouts particularly during momentary power interruptions 7 To shut down the heater turn off the gas and...

Page 16: ...er orifice and clean it thoroughly 4 Check the venturi opening to be sure it is clean If there is any evidence of dirt accumulation in the venturi remove it 15 BURNER OPERATION TROUBLESHOOTING A IGNIT...

Page 17: ...The thermostat sensing bulb is incorrectly placed The thermostat is out of calibration Conduct heat loss and add heaters or other source of heat as necessary Reposition as necessary for proper operat...

Page 18: ...Form 43219040 Oct 2013 C TROUBLESHOOTING CHART Continued 17...

Page 19: ...RD030 RD033 RD035 RD040 43822010 RD060 RD066 RD070 RD080 43822020 RD100 RD120 43822030 RD132 RD140 RD160 43822040 17 OPTIONAL PROTECTIVE REVERB SCREEN The optional protective Reverb Screen acts as a s...

Page 20: ...D060 RD066 RD070 RD080 26 43872980 Orifice 3 32 for RD030 RD060 Natural Gas 11 43862030 Manifold for RD100 RD120 27 43872520 Orifice 52 for RD033 RD066 RD100 RD132 Propane Gas 12 43862040 Manifold for...

Page 21: ...Form 43219040 Oct 2013 21 WARNINGS CARD This card is furnished with each heater Additional copies may be ordered under part no 43344970 20...

Reviews: